Cascade And Zone Regulator Diagram Of Connections And Terminals - Immergas VICTRIX PRO 1 I Series Technical Sheet

Wall-hung modular condensing boilers for high power
Table of Contents

Advertisement

48
DIAGRAM OF CONNECTIONS AND TERMINALS
There are terminal blocks on the back of the cascade and zone
regulator dedicated to the network connections and the low
voltage connections.
Connection to the network.
1 - Relay outlet (not used)
2 - Relay input (not used)
3 - Direct heating circuit pump (CD)
4 - N.C. (not used)
5 - D.H.W. pump
6 - L 1/ 230 V (power supply)
7 - Mixed circuit valve (CMI-1) OPEN
8 - Mixed circuit valve (CMI-1) CLOSED
9 - Mixed circuit circulation pump 1
10 - Variable outlet relay 1
11 - Variable outlet relay 2
12 - L 1 230/V
13 - Mixed circuit valve (CMI-2) OPEN
14 - Mixed circuit valve (CMI-2) CLOSED
15 - Mixed circuit circulation pump 2
16 - N.C.
17 - Relay outlet (not used)
18 - Relay input (not used)
19 - (not used)
20 - (not used)
21 - N/230V mains power supply
22 - L1 /230V mains power supply
66
CASCADE AND ZONE REGULATOR
VICTRIX PRO 1 I
Some parts belonging to the heating control unit must be con-
nected to the respective terminal blocks.
Low voltage connections.
23 - Common GND
24 - Signal data bus connection A (zone controls and room
thermostats)
25 - Signal data bus connection B (zone controls and room
thermostats)
26 - External probe (PTC)
27 - (do not use)
28 - Domestic hot water probe (PTC)
29 - Mixed circuit flow probe 1 (PTC)
30 - Variable input 1
31 - Variable input 2
32 - Variable input 3
33 - Mixed circuit flow probe 2 (PTC)
34 - Solar panel probe (PT1000)
35 - Solar storage tank probe (PTC)
36 - Pulse input
37 - Boiler data bus A
38 - Boiler data bus B
Bus address (Cascade manager).
If there is only one regulating unit, it is always assigned bus
address 10. When there are multiple connected regulating
units (maximum of 8), the regulator that is connected di-
rectly to the boiler must be assigned address 10. The other
regulators must be assigned addresses with progressive
numbers, such as 20, 30, 40 and 50.