Technical Data - Immergas VICTRIX PRO 1 I Series Technical Sheet

Wall-hung modular condensing boilers for high power
Table of Contents

Advertisement

VICTRIX PRO 35 1 I - 55 1 I
43
Maximum nominal heat input
Maximum nominal effective output (80/60°C)
Maximum nominal effective output (50/30°C)
Minimum nominal heat input
Minimum nominal effective output (80/60°C)
Minimum nominal effective output (50/30°C)
Efficiency at 100% Pn (80/60°C)
Efficiency at 30% of the load (80/60°C)
Efficiency at 100% Pn (50/30°C)
Efficiency at 30% of the load (50/30°C)
Efficiency at 100% Pn (40/30°C)
Efficiency at 30% of the load (40/30°C)
Central heating circuit
Adjustable central heating system temperature
Max system operating temperature
Max system operating pressure
Available head with flow rate of 1000 l/h
Gas supply
Fan speed METHANE (G20)
Fan speed LPG (G31)
Gas flow rate to the burner METHANE (G20)
Gas flow rate to the burner LPG (G31)
Electric power supply
Nominal power absorption
Installed electric power
Power absorbed by fan
Power absorbed by pump
Electrical insulation rating
Boiler water capacity
Weight of empty boiler

TECHNICAL DATA

kW (kcal/h)
kW (kcal/h)
kW (kcal/h)
kW (kcal/h)
kW (kcal/h)
kW (kcal/h)
%
%
%
%
%
%
°C
°C
bar
kPa (m H
MIN - MAX
RPM
MIN - MAX
RPM
MIN - MAX
m
/h
3
MIN - MAX
kg/h
V/Hz
A
W
W
W
IP
litres
kg
VICTRIX PRO 35
34.9 (30,051)
34.0 (29,240)
37.3 (32,155)
3.9 (3,388)
3.4 (2,924)
3.7 (3,208)
97.3
99.0
107.0
106.1
107.3
103.8
20-85
90
4,4
O)
46.3 (4.72)
2
1000 - 5050
1000 - 4900
0.42 - 3.70
0.31 - 2.71
230 - 50
0.9
140
28
98
X5D
2.8
51.2
VICTRIX PRO 55
51.3 (44,098)
49.9 (42,914)
54.8 (47,097)
5.5 (4,715)
5.0 (4,300)
5.5 (4,701)
97.3
101.1
106.8
106.3
107.4
105.9
20-85
90
4,4
46.3 (4.72)
1100 - 6550
1050 - 6450
0.58 - 5.43
0.43 - 3.98
230 - 50
1.0
195
73
98
X5D
2.8
51.4
53