Hydraulic Separator Kit For Individual Boiler Victrix Pro 35 1 I - 55 1 I - Immergas VICTRIX PRO 1 I Series Technical Sheet

Wall-hung modular condensing boilers for high power
Table of Contents

Advertisement

12
HYDRAULIC SEPARATOR KIT FOR INDIVIDUAL BOILER
The hydraulic separator (compensator) is a particularly signif-
icant part inside the hydraulic circuits.
It is an open manifold (2) which places system flow and return
in communication, creating 2 circuits: a primary circuit (boiler
- manifold) and a secondary circuit (manifold-system).
The former circulates by the boiler pump, while the latter runs
on the correct thermal gradient (and therefore the correct water
flow rate), as defined by the system's design.
It is advisable to include a hydraulic compensator (2) every time
the overall flow rate required by the system is greater than what
the boiler is able to supply. The maximum flow rate at the inlet
is the generally adopted sizing method.
1
1
2
3
G2"1/2
16
VICTRIX PRO 35 1 I - 55 1 I (CODE 3.023951)
M
R
G1"1/2
G2"1/2
4
6
Sludge filter head loss graph
The brass sludge collecting filter, with relative inspectable
stainless steel cartridge, protects the condensation module from
getting clogged with the sludge or build-up from the system.
Attention: The boiler has an IPX5D electric insulation rating
and can also be installed outdoors, without additional protec-
tions. However, if installed outdoors, the relevant piping should
be insulated.
KEY:
1
- Gasket 44x34x2
2
- Insulated Hydraulic manifold DN 100
3
- Gasket 72x55x2
1
4
- 90° fitting
5
- 2" Nipple
6
- Slurry collection brass filter
M - Flow
R
- Return
3
5
Flow rate (I/h)
M-M
1 /
2

Hide quick links: