INSTALLATION
− Unscrew the vent valve's release cap
− Open the shut-off cocks in order to slowly fill the system
− Use the pressure gauge to check that the pressure is rising
and the water is exiting through the vent valves
− Close the shut-off cocks after the pressure reaches 1.5 bar
− Start the system pumps and the thermal module's pump
as shown in Paragraph "Commissioning and mainte-
nance"
− During this stage, check that the air is correctly eliminat-
ed
− Restore the pressure if necessary
− Switch the pumps off and on again
− Repeat the last three steps until the pressure is stabilised
9
The system must be filled up slowly the first time; once it is
filled and the air expelled it should never need to be topped
up again.
9
Systems should also be operated at maximum working
temperature the first time they are started up, in order to
facilitate de-aeration. (Gas is not released from the water at
low temperatures).
9
An automatic spurge can be performed during the first igni-
tion. The parameter that set the cycle is Par. 139. See param-
eter table for more information.
2.12.2

Emptying

Before starting to empty the appliance and the storage cylinder:
− Switch the system's master switch to the OFF position and
the thermal module's master switch to (0).
− Close the water supply shut-off cocks;
− In order to empty the appliance, fit a rubber hose (2) (in-
ner diameter int. Ø = 12 mm) to the thermal module's
discharge valve (1).
Condexa PRO 35 P - Condexa PRO 50 P
1
2
Condexa PRO 57 P ÷ Condexa PRO 135
1
2
28