Holiday setting
Holiday Settings
"
"
Mode
"
"
Group
"
"
Enables the user to change parameters for the Holiday Pro-
gramme.
Mode
Select the Holiday programme mode. It can be set to Off, System
or group.
Off
Disabled programme
Group
it enables the selection of the group (1 – 8).
As part of group selection, the Holiday Group is displayed with
the following parameters:
− Holiday set-point: Set-point type to be used for the se-
lected group. All zones in this group shall use this set-
point if the current date is between the start and end
date of the holiday period, but only if the group is en-
abled in the group settings menu, and can be selected
from: Off, Comfort, Eco, Anti-freeze and Reduced.
− Start date / End date (Day DD-MM-YEAR):
External Zone
DHW -
Period
Group
DHW
"
"
"
"
"
Active Day(s)
Program Comfort Period
Sunday
"
"
"
"
Interval 1
Comfort Setpoint
00:00
"
"
"
"
Interval 2
ECO Setpoint
00:00
"
"
"
"
Interval 3
Out of interval setpoint
00:00
"
"
"
"
− System: It enables the user to select the holiday pro-
gramme for the entire system. In this mode, the set-
point is common to all system groups.
External Zone
Group
DHW
DHW -
Period
"
"
"
"
"
Active Day(s)
Program Comfort Period
Sunday
"
"
"
"
Interval 1
Comfort Setpoint
00:00
"
"
"
"
Interval 2
ECO Setpoint
00:00
"
"
"
"
Interval 3
Out of interval setpoint
00:00
"
"
"
"
− Holiday set-point (hidden if the Mode is set to "Off"):
Type of reference to be used when system mode is select-
ed. This set-point is used for all areas. Only used for the
holiday system.
Group
"
"
1
1
"
71
"
"
00:00
28.0
°C
"
"
20.0
00:00
°C
"
"
00:00
Reduced
"
"
1
"
71
"
"
28.0
00:00
°C
"
"
20.0
00:00
°C
"
"
Reduced
00:00
"
"
Seasonal setting
Enables the user to change parameters for the Seasonal Pro-
gramme.
The seasonal programme is used to define a period of inactivity
for the heating system. This menu includes the following ele-
ments:
Activates heating basis
Selects how the seasonal programme must verify whether heat-
ing can be allowed or not. It can be set on:
− Always: it means that the seasonal programme is ignored
and (CH) heat demand is always allowed throughout the
year.
Season Settings
"
"
Mode
"
"
− At date: excludes heating (CH+zone) when the current
date is included between the start and the end dates.
Season Settings
"
"
Mode
"
"
Begin Date
"
"
End Date
"
"
− At Temp: excludes heating (CH+zone) when the outdoor
temperature is higher than the selected temperature.
(Ext. deactivation T: 0.0 °C/50 °C)
Season Settings
"
"
Mode
"
"
Outdoor Temp. Below
"
55
COMMISSIONING AND MAINTENANCE
Off
"
"
On Date
"
"
15-04
15-09
On Temp
"
"
25.0
°C
"
"
"