Setting Zone's Climatic Curve Parameters (Accessible Only With Installer Password); Programming The Zone - Riello Condexa PRO Series Installation, Technical And Maintenance Manual

Table of Contents

Advertisement

MANAGING ADDITIONAL ZONE
4.4 Setting zone's climatic curve parameters
(accessible only with installer password)
Menu → "Settings" → "Zone Clim. Curve"
− press the ► key so that the number is highlighted on the
right of the word "Zone";
− use the ▲ and ▼ keys to change the zone number;
− press the ● key.
The following is displayed:
Outdoor reset
"
"
194
32
5
T Outside [°C]
"
The "Comp. T. @ T.ext. Max" parameter, if other than 0, trans-
forms the climatic curve from linear to quadratic allowing you to
best adapt the variation of the setpoint to the variation of the
outdoor temperature.
The resulting quadratic climatic curve will have three parame-
ters:
− Heat. Set. Max
− Baseline Outdoor Temp.
− Text. Min
of the basic linear climatic curve and a value of the Heat. Set.
Min. diminished by the value of the parameter "Comp. T. @
T.ext. Max", as can be seen in the example in the figure.
Delivery Temp.
(°C)
Max. Heating Set.
Min. Heating Set.
Baseline Outdoor Temp.
Min Outdoor Temp.
Des. Supply T.
82.0
"
"
Bas. Supply T.
40.0
"
"
WW Shutdown
21.0
"
"
Bas. Outd. T.
21.0
95
"
"
Des. Outd. T.
-4.0
"
"
"
Comp. T. @ T.ext. Max
Outdoor Temp. (°C)
Shutdown Temp.
4.5

Programming the zone

By default the schedule timer is disabled.
In fact, to start a request from the zone just close the contact
of the zone request. In this case the thermal module (or the
cascade of thermal modules) will start with a setpoint equal to
the value calculated on the zone climatic curve increased by the
"Zone Extra Setpoint" value and the mix valve will modulate to
maintain the delivery temperature of the zone at the calculated
setpoint.
To activate zone programming:
°C
Menu → "Settings" → "Time Config."
"
"
°C
"
"
°C
Settings
"
"
°C
"
"
Clock Settings
"
"
°C
"
Appliance Configuration
"
"
"
External Zone Settings
"
Ext. Zone Climatic Curve
"
Confirming with ● the following screen is displayed:
Clock Settings
"
CH Clock
"
"
DHW Clock
"
CH Ext. Zones Clock
"
− with the ▲ / ▼ keys select "CH Zones time"
− with the ► key move to "Disabled", change it to "Ena-
bled" with the ▲ / ▼ keys
− confirm with the ● key
Go to:
Menu → "Schedule timer"
Confirming with the ● key:
Clock Program
"
Program CH Zone Ext.
"
Program Group
"
Holiday Settings
"
Season Settings
"
At this point select the number of the zone to be programmed
and confirm with the ● key.
External Zone
"
Program Comfort Period
"
Comfort Setpoint
"
ECO Setpoint
"
Out of interval setpoint
"
72
p
"
"
"
"
"
Disabled
"
Disabled
"
"
Disabled
"
"
"
1
"
1
"
"
"
1
"
1
"
20.0
"
5.0
°C
"
"
Anti Fr
"
"
"
"
"
°C
"
"
"
"

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents