System Filling And Emptying; Water Quality Requirements - Riello INSIEME EVOe 32 B/110 LN Installation And Maintenance Manual

Hide thumbs Also See for INSIEME EVOe 32 B/110 LN:
Table of Contents

Advertisement

T
C
A
Type C transformation accessory
B
Concentric flue kit
C
Condensation exhaust system (not supplied)
T
Terminal
L
Maximum straight length
(This length must be reduced by 1 metre for every 90°
curve and by 0.5 metres for every 45° curve.)
Description
L
MAX
(*) This length must be reduced by 1 metre for every 90° curve
and by 0.5 metres for every 45° curve.
9
Use of flues longer than the specified maximum leads to a
loss of heat output from the boiler.
9
Never obstruct or choke the comburent air intake pipe.
1m
L
B
A
INSIEME EVOe 32 B/110 LN
7 (*)

2.11 System filling and emptying

The thermal unit INSIEME EVOe 32 B/110 LN is equipped with an
internal system load valve (1), which can be reached by remov-
ing the front panel.
Before performing any system filling or emptying operation, set
the system main switch to OFF and the equipment main switch
to (0).
2.11.1

Water quality requirements

The manufacturer recommends the use of water as heat transfer
m
fluid for the central heating system. A chemical treatment sys-
tem must be provided for this water.
The heat transfer fluid (water) for the central heating circuit must
conform to the quality parameters given in the following table:
pH
Electrical conductivity
Chlorine ions
Sulphuric acid ions
Total iron
Alkalinity M
Total hardness
Sulphur ions
Ammonia ions
Silicon ions
If the hardness of the water exceeds the value specified in the
table, it is mandatory to install a water softening system.
9
Excessive water softening (leading to a total hardness < 15°F)
can cause corrosion in metal parts (pipes and boiler com-
ponents). Keep the electrical conductivity of the water un-
der 200 μS/cm.
0
Do not top up the central heating circuit on a frequent or
continuous basis as this can damage the boiler's heat ex-
changer. The use of automatic topping up systems should
be avoided for this reason.
23
1
REFERENCE VALUES
6-8
less than 200 μS/cm (25°C)
less than 50 ppm
less than 50 ppm
less than 0.3 ppm
less than 50 ppm
less than 35°F
none
none
less than 30 ppm
INSTALLATION