Parameters' List - Riello Condexa PRO Series Installation, Technical And Maintenance Manual

Table of Contents

Advertisement

2.15.2

Parameters' list

Parameters are listed base on the reference menu.
Reference Menu
M1
Parameters Menu
M2
Cascaded module configuration menu
M3
Cascaded boiler configuration menu
M4
Appliance configuration menu
Nr. dis-
Par.
Menu
played
No.
Display
Defines the thermal module's various heating
M1
1
CH mode
CH set-
Defines the desired delivery temperature in heating
M1
3
point
Calc.
Establishes the set-point offset value calculated in
M1
109
set-point
climatic mode (Par. 1= 1). Offsets the climatic curve
off-set
CH Min.
Sets the minimum delivery temperature value in
M1
110
Set-
point
CH Min.
Sets the maximum delivery temperature value in
M1
111
Set-
point
Sets the overrun time in seconds of the boiler's
Boiler
circulator during stand-alone operation; cascaded
M1
5
Pump
operation determines the module's overrun after
Overrun
Sets the activation temperature when the maxi-
mum flue gas temperature is exceeded. When the
flue gas temperature is higher than a set value,
Flue
the module switches off and an error message is
M1
6
Temp.
generated. When the flue gas temperature is in
Limit
the interval between (Par. 6) -5°C and Par. 6, the
module reduces its power in a linear way until it
reaches minimum power when the temperature
Sets the value in degrees beyond the set-point at
CH Hys-
M1
7
which the burner switches off for thermoregula-
teresis
CH Hys-
Sets the value in degrees below the set-point at
M1
112
teresis
which the burner switches on again for thermoreg-
Down
Sets the stand-by time before the appliance is
An-
switched on again after it switches off due to
M1
9
ti-cycle
thermoregulation, independently from the delivery
Period
temperature dropping below the value indicated in
Par. 10. Parameter valid only in stand-alone mode.
Anti-cy-
Sets the value in degrees below which the burner
M1
10
cle Temp.
switches on again notwithstanding from the time
Diff.
Sets the value of the temperature difference (Delta
T) between the module's delivery and return tem-
perature. For a Delta T value ranging between Par.
12 and (Par. 12) +8°C, the module reduces its power
Hx diff.
in a linear fashion until it reaches the minimum
M1
12
Mini-
power. The minimum power is maintained until
mum
reaching (Par. 12) +8°C+5°C, after which the module
switches off for a period of time equal to the value
attributed to Par. 13; at the end of this time interval,
Hx Diff.
Max.
Defines the restart time after reaching the Delta T
M1
13
Wait
Time
Max.
M1
14
Power
CH
Description
operation modes.
mode (Par. 1) = 0.
in presence of mild outdoor temperatures.
heating mode (Par. 1) = 4.
heating mode (Par. 1) = 4.
switch-off due to temperature control.
measured is equal to Par. 6.
tion.
ulation.
spent at Par. 9.
the module switches on again.
limit between delivery and return.
Sets the heating's % max. power.
Access type
U
End user
I
Installer
O
Manufacturer
Range
0...5
Par. 23...Par. 24
Off, -10...10
20...50
50...90
0...900
10...120
0...20
0...20
10...900
0...20
10...60
10...250
50...100
41
INSTALLATION
Default
Access
UM
Category
setting
type
0
I
70
°C
U
0
I
30
°C
I
80
°C
I
60
Sec.
I
100
°C
O
5
°C
I
5
°C
I
120
Sec.
I
16
°C
I
40
°C
O
30
Sec.
O
100
%
I
Heating
Heating
Heating
Heating
Heating
Heating
General
Heating
Heating
Heating
Heating
General
General
Heating