Water connections

The dimensions and position of thermal module's hydraulic connections are shown in the table below.
Front view
RI
DESCRIPTION
A
B
C
D
E
F
H
(optional 3-way valve
attachment)
MI
(system flow)
RI
(system return)
SC
(condensate drain)
G
(gas inlet)
9
Before connecting the thermal module the protection plugs
must be removed from the delivery, return and condensate
drain pipes.
9
Before connecting the thermal module, it is necessary to
clean the system. This step is absolutely required when the
appliance replaces another one on pre-existing systems.
In order to carry out this cleaning activity, if the old generator is
still installed on the system, it is advisable to:
− add a de-scaling additive.
− Operate the system with the generator on for around 7
days.
− Discharge dirty system water and flush the system one or
more times with clean water.
MI
35 P
50 P
57 P
387
387
387
143,5
143,5
143,5
63,5
63,5
63,5
283,5
283,5
283,5
98,5
98,5
98,5
92,5
92,5
92,5
202,5
202,5
-
G 1" 1/2 M G 1" 1/2 M G 1" 1/2 M G 1" 1/2 M G 1" 1/2 M G 1" 1/2 M G 1" 1/2 M G 1" 1/2 M
G 1" 1/2 M G 1" 1/2 M G 1" 1/2 M G 1" 1/2 M G 1" 1/2 M G 1" 1/2 M G 1" 1/2 M G 1" 1/2 M
25
25
25
G 1" M
G 1" M
G 1" M
Bottom view
RI
Condexa PRO
70 P
90
387
387
143,5
143,5
63,5
63,5
283,5
283,5
98,5
98,5
92,5
92,5
-
-
25
25
G 1" M
G 1" M
If the system is very dirty, repeat the last procedure one more
time.
If the old generator is not present or available, use a pump to
circulate the water + additive through the system for about 10
days and perform a final washing as described in the previous
paragraph.
Once the cleaning has been completed, it is recommended to
add a suitable protective fluid to the system's water before in-
stalling the thermal module.
In order to clean the heat exchanger's built-in water system,
please contact Technical Assistance Service
0
Do not use incompatible liquid detergents, including acids
(for instance, chloridric acid and similar) in any concentra-
tion.
0
Do not subject the heat exchanger to cyclical pressure
changes because fatigue stress is very dangerous for the in-
tegrity of system components.
19
INSTALLATION
A
B
C
G
MI
D
E
SC
F
H
100
115
135
387
387
387
143,5
143,5
143,5
63,5
63,5
63,5
283,5
283,5
283,5
98,5
98,5
98,5
92,5
92,5
92,5
-
-
-
25
25
25
G 1" M
G 1" M
G 1" M
R
.
mm
mm
mm
mm
mm
mm
mm
Ø
Ø
Ø mm
Ø

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents