Riello Condexa PRO Series Installation, Technical And Maintenance Manual page 45

Table of Contents

Advertisement

Nr. dis-
Par.
Menu
played
No.
Display
Flow
M1
129
sensor
Mod.
Defines the delta T set for the operation of the
M1
133
Pump dT
Mod.
Defines the time in seconds from the moment the
Pump
burner is switched on to start the modulation of
M1
134
Start
the circulator and obtain the delta T specified in
Time
Mod.
M1
135
Pump
Defines the PWM circulator model installed.
Type
Mod.
Defines whether the boiler's circulator operates in
M1
136
Pump
modulating mode or at a set speed (as a percent-
Mode
Mod.
Defines the percentage of speed that sets the min-
M1
137
Pump
imum speed that the circulator can reach during
Min Pwr
Value can vary depending on appliance configura-
Appli-
tion based on Par. 97 and 98. This value is calculat-
M1
138
ance
ed by the board, which, based on an internal logic,
type
defines as a single number the settings of Par. 97
Activates bleeding the system's air. To activate air
bleeding, it is necessary to switch on the boiler
and change the parameter from "No" to "Yes".
Wait for one minute. Switch off and restart. At this
stage, when it is restarted the boiler will initiate
Dair
the automatic bleeding procedure (lasting around
M1
139
active
20 minutes). With the parameter set to "Yes", the
procedure is carried out each time the boiler is
switched off and restarted using its master switch.
The value must be set to "No" if you do not wish to
initiate the bleeding procedure when the thermal
Mini-
Defines the flow rate below which the boiler is
M1
140
mum
switched off. The value varies depending on the
Flow
Anti-Le-
Sets the weekday on which the anti-Legionella
M1
107
gionella
day
Anti-Le-
Sets the time of the day during which the anti-Le-
M1
108
gionella
Hour
Activates the emergency mode. This mode comes
Permit
on when communication between Managing and
Emer-
the primary circuit's probe is lost. In this event,
M2
72
gency
if Par. 72 is set to "Yes", the cascade is initiated,
Mode
working to the fixed set-point determined by Par.
Emer-
M2
74
gency
Set-point
Delay
Per Start
Defines the stand-by time in seconds to restart the
M2
75
Next
subsequent cascade module in normal start mode.
Mod.
Delay Per
Defines the stand-by time in seconds to switch off
M2
76
Stop Next
the last cascade module on in normal Off mode.
Mod.
Delay
Quick
Defines the stand-by time in seconds to restart the
M2
142
Start
Next
Description
Defines the type of flow sensor used.
modulating circulator.
Par. 133.
age of maximum speed).
modulation.
and 98.
module is switched on.
model.
procedure is carried out.
gionella procedure is carried out.
74.
Set-point active in emergency mode.
next cascade module in quick start mode.
Range
Bitron, Huba:
DN8, DN10, DN15,
DN15, DN20, DN25
5...40
0...255
0 = Wilo
1 = Salmson
2 = Grundfos
On/Off Modulat-
ing Fixed 20...
100%
0...100
0...255
Yes, No
0.0...100
Sun...Sat.
0...23
Yes/No
20...65
5...255
5...255
5...255
45
INSTALLATION
Default
Access
UM
setting
type
Huba
I
DN25
15
°C
I
120
Sec.
I
2 =
I
Grundfos
Modulat-
I
ing
30
%
I
Depends
on boiler
I
model
No
I
Depends
on boiler
l/min
I
model
Sun
Day
I
0
Hour
I
Yes
U
70
°C
I
120
Sec.
I
30
Sec.
I
60
Sec.
I
Category
General
General
General
General
General
General
General
General
General
DHW
DHW
Cascade
Cascade
Cascade
Cascade
Cascade