LEMCOM CANopen® – User manual
12.22
3012h – Restore factory settings
Any given module or all of an island's modules can be reset to their factory settings by sending the
following message:
CAN-ID
Command
(600h+ID)
2Fh
620h
Byte 0 is used to define the module to reset:
- Byte 0 = 0x00 Reset parameters of master module (address #0)
- Byte 0 = 0x01 Reset parameters of secondary module at address #1
- ...
- Byte 0 = 0x0F Reset parameters of secondary module at address #15
- Byte 0 = 0x10 or higher Reset parameters of all modules on the island
The factory settings are the following:
L1/h1
L2/h2
Automatic blowing
Automatic blowing duration (ms)
ASC
DIAG ECO
Max. number of bounces (DIAG/E)
DIAG/ECO assessment time (s)
Blue LED mode
Valve status (if comm. lost)
COVAL – LMCOP-EN-A-1155UM0068
Object L
Object H
12h
30h
LEMC60X...
60% vacuum max.
35%/10%
45%/10%
Table 15 – Factory settings
Detailed description of CANopen objects
Subindex
Byte 0
00h
Module no.
OFF
500
ON
ON
2
1
BL1
MD1
Byte 1
Byte 2
Byte 3
00h
00h
LEMC90X...
85% vacuum max.
65%/10%
75%/10%
00h
39/49