LEMCOM CANopen® – User manual
Recommendations
The Venturi pump parameters can be adjusted in order to perfectly meet the requirements of certain
applications. In this case, we recommend observing the following conditions:
-
L2-h2 > L1
threshold
-
h1 < L1
threshold
-
h2 < L2
threshold
-
When handling porous materials, deactivate the ASC in order to reduce solenoid
and suction valve wear.
WARNING IF SETTINGS ARE WRONG
If the above conditions are not observed, the MS LED of the corresponding module
flashes red.
COVAL – LMCOP-EN-A-1155UM0068
i.e. the control range must be higher than the "part gripped"
i.e. the hysteresis h1 must be lower than the part gripped
i.e. the hysteresis h2 must be lower than the control
General overview of LEMCOM
9/49