7.7 Alarms and warnings

Module
Name
Description
3
WarningCode
Code for booster system warning.
4
FaultCode
Code for booster system alarm.
In the WarningCode module, the cause of a booster system
warning can be read. A warning has no influence on the booster
system operation.
In the FaultCode module, the cause of a booster system alarm
can be read. A booster system alarm always leads to a reaction in
the booster system operation, usually all pumps are stopped, but
some Hydro MPC or Control MPC alarms have programmable
alarm action types.
The complete list of possible alarm and warning codes is shown
below.
Code
Alarm/warning description
3
External fault signal
10
Communication fault, pump
80
Hardware fault, IO 351 pump module
80
Hardware fault, IO 351 I/O module
83
Verification error, EEPROM parameter area
88
Sensor fault, general measuring sensor
89
Signal fault, closed-loop feedback sensor
91
Temperature sensor 1 signal fault
157
Real Time Clock error
161
Sensor supply fault, 5 V
162
Sensor supply fault, 24 V
165
Signal fault, analog input A1
166
Signal fault, analog input A2
167
Signal fault, analog input A3
175
Temperature sensor 2 signal fault
190
Limit exceeded, supervised item 1
191
Limit exceeded, supervised item 2
203
Alarm on all pumps
204
Inconsistency between sensors
208
Operation outside performance range
210
High pressure
211
Low pressure
213
VFD not ready
214
Water shortage
215
Soft pressure buildup timeout
216
Pilot pump alarm
219
Pressure relief not adequate
231
Ethernet: No IP address from DHCP server
232
Ethernet: Auto-disabled due to misuse
248
Fault, battery/UPS
Pump alarms. See section
From device
modules 29 to
1)
For Hydro/Control MPC and Multi-E model H and later, it can
be automatic (A) or selectable Automatic/Manual (A/M).
2)
For Hydro/Control MPC and Multi-E model H and later, it can
be none or programmable (Prog.).
Event action programmable are Stop, Stop with delay, Min.,
UserDef, Max., Pumps in local, Emergency run.
The Hydro Multi-E model G is always stopped in case of an
alarm.
7.9 Zone pump modules (ZonePumpModule,
34).
Pumpland.ru
1)
Reset type
Action type
A/M
Prog.
A
None
A
None
A
None
A
None
A
None
A/M
Prog.
A/M
Prog.
A
None
A
None
A
None
A/M
Prog.
A/M
Prog.
A/M
Prog.
A/M
Prog.
A/M
Prog.
A/M
Prog.
A/M
Prog.
A
None
A/M
Prog.
A/M
Prog.
A/M
Prog.
A
None
A/M
Prog.
A/M
Prog.
A
None
A
None
A
None
A
None
A
None
-
None
2)
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents