GRUNDFOS INSTRUCTIONS PROFIBUS and PROFINET for Digital Dosing CIM 150 PROFIBUS DP CIM 500 Ethernet for PROFINET IO Functional profile and user manual...
5.5 Termination resistors 5.6 Status LEDs 1.2 Notes 5.7 Communication watchdog The symbols and notes below may appear in Grundfos 5.8 Reaction to PLC "Stop button" installation and operating instructions, safety instructions and PROFINET IO, CIM 500 setup service instructions.
Separated or Safety Extra-Low Voltage with ’DDA pump’ in this document. SELV-E earth connection. Grundfos cannot be held responsible for any problems caused SubMiniature version A. Coaxial radio signal directly or indirectly by using information in this functional profile. cable connection standard.
3. System description The system diagram provide an overview of the two different technologies and how to connect the CIM module to the Grundfos DDA E-box that you connect to a PROFIBUS DP or PROFINET IO network. CIM 150/500 is a communication module installed internally in the Grundfos DDA E-box using a 10-pin connection.
PROFINET IO. 6.5 Status LEDs 4.2 CIM 150 PROFIBUS DP The table below provides an overview of the specifications for Grundfos CIM 150. For further details, refer to the specific sections of this functional profile. PROFIBUS DP specifications Description...
5. PROFIBUS DP, CIM 150 setup 5.3 Connecting the PROFIBUS 5.3.1 Data transmission rates and cable length 5.1 PROFIBUS bus topology We recommend using a cable according to IEC 61158. The PROFIBUS-preferred bus topology is daisy chaining as Example illustrated in fig. 2. The end devices of a physical bus segment must be terminated (LT = Line Termination).
5.4 Setting the PROFIBUS address 5.6 Status LEDs Select the PROFIBUS address via the menu system in the pump The CIM 150 PROFIBUS module has two LEDs. See fig. 3. display. • Red and green status LED1 for PROFIBUS communication. •...
6. PROFINET IO, CIM 500 setup 6.2 Setting the Industrial Ethernet protocol The CIM 500 ethernet module has a rotary switch for selection of 6.1 Connecting the ethernet cable the Industrial Ethernet protocol. See fig. 9. CAUTION Electric shock Minor or moderate personal injury - Connect CIM 500 only to SELV or SELV-E circuits.
CIM 500 and the Grundfos product. • Configure the PC ethernet port to the same subnetwork as CIM 500 does not support the Grundfos Permanently red CIM 500, for example 192.168.1.101, and the subnet mask to product connected. 255.255.255.0. See section A.2 Web server configuration...
This is a PROFIBUS/PROFINET output module used for the 7.1 Data types control of the DDA pump. Its data type is 10, non-standard. Grundfos CIM 150/500 supports the following data types. Mode/state settings All data types, except for data type 10, comply with specification...
Page 11
7.2.1 Explanation of control bits in ControlModule Velocity Control bit used to select SlowMode suction stroke velocity. RemoteAccessReq Control bit used by CIM 150/500 to activate control from the bus. Select SlowMode velocity 50 %. Select SlowMode velocity 25 %. The pump can only be controlled via the pump HMI and from its external signal inputs.
Page 12
AutoFlowAdaptEnable 7.2.3 Explanation of operating mode The AutoFlowAdapt function detects changes in various Control enumeration for selection of operating mode. parameters and responds accordingly to keep the flow constant. Dosing accuracy is increased when this function is enabled. Value Name AutoFlowAdapt function disabled.
7.3 Dosing settings Module Name Data type Unit Description Setting of the setpoint used in operating mode "Manual". SetSetpointManual Can also be set via the pump HMI. The present value can always be read from ActSetpointManual (module 12). Setting of the pulse volume used in operating mode "Pulse". SetPulseVolume Can also be set via the pump HMI.
7.5 Bus settings compared to pump HMI settings 7.6 Status module (StatusModule, module 11) This is a PROFIBUS/PROFINET input module used for the status Selectable Setting preserved of the DDA pump settings. Its data type is 10, non-standard. The Name from HMI during power-off actual status of all the pump modes and states are reflected, no...
Page 15
7.6.1 Explanation of status bits ActProfiWatchdogEnable Status bit indicating whether the PROFIBUS/PROFINET software ActRemoteAccess watchdog has been enabled. Status bit indicating whether the pump is in a state where it is controllable from the bus. 0: PROFIBUS/PROFINET software watchdog disabled. 1: PROFIBUS/PROFINET software watchdog enabled.
Page 16
7.6.2 Explanation of command acknowledge bits 7.6.3 Explanation of ActualOperatingMode If the ActRemoteAccess bit is not set, PROFIBUS/PROFINET Status enumeration for reading of the actual operating mode. For commands (and writings in general) will be prohibited and none of an explanation of these modes and the belonging enumeration, the acknowledge bits will ever be set.
7.7 Measurement data modules Module Name Data type Unit Description The actual setpoint used in operating mode "Manual". ActualSetpointManual Can be set via SetpointManual (module 2) or via the pump HMI. The actual pulse volume used in operating mode "Pulse". ActualPulseVolume Can be set via SetPulseVolume (module 3) or via the pump HMI.
Page 18
Module Name Data type Unit Description Status of the external digital inputs. Logical "0": The input is not active. Logical "1": The input is active. DigitalInputs Bits The relay input type (NO or NC) is selected via the pump HMI. Signals are fixed to the following: Bit 0: Low-level signal Bit 1: Empty signal...
7.8 Alarms and warning Module Name Data type Description Code for active pump alarm. FaultCode See event code in the table below. Code for first active pump warning. WarningCode See event code in the table below. All active warnings. The belonging event code in parenthesis. Byte 1 Bit 0:Backpressure low (211)* Bit 1:Air bubbles (35)*...
30: Smart Digital Dosing, DDA 1: Smart Digital Dosing, DDA 1: With 3-phase pumps 39: Hydro Multi-E model H and later models 2: With 1-phase pumps UnitType [enumeration] According to description above. UnitVersion [enumeration] Used by Grundfos. CIMSoftwareVersion [number] CIMSoftwareRevision [number] CIMModel [enumeration]...
8. Product simulation The CIM module can be put in product simulation mode in which case it will generate life-like simulated values of all the PROFIBUS/PROFINET input data modules. It will thus be possible to connect a PROFIBUS/PROFINET master to CIM 150/CIM 500 without this device being connected to a real pump in a real-life system.
CIM 500 and the Grundfos product. Grundfos product. 4. LED2 for internal communication is a) CIM 500 does not support the Grundfos Contact the nearest Grundfos company. permanently red. product connected. 5. The PROFINET IO LED1 is permanently a) Connected Grundfos product is not Contact the nearest Grundfos company.
Page 23
10. Grundfos alarm and warning codes This is a complete list of alarm and warning codes for Grundfos products. For the codes supported by this product, see the alarms and warnings section. Code Description Code Description Code Description Motor temperature 2 (Pt100,...
Page 24
Code Description Code Description Code Description Electronic inverter protection Signal fault, temperature sensor 3 activated (EIP) (t_mo3) Signal fault, Smart trim gap sensor Signal fault, vibration sensor Signal fault, bearing temperature Motor temperature 3 (Pt100, sensor (Pt100), general or top t_mo3) bearing Bearing temperature high (Pt100),...
Page 25
Code Description Code Description Code Description Low pressure Communication fault, I/O module Motor phase failure Diaphragm tank precharge Automatic motor model recognition Combi event pressure out of range failed Motor relay has been forced VFD not ready Night flow max. limit exceeded (manually operated or commanded) Water shortage, level 2...
Page 26
Appendix The appendix describes the parts of the CIM 500 web server needed for the configuration of a PROFINET IO Ethernet connection. For other CIM 500 web server features, not specifically related to PROFINET IO, see the installation and operating instructions for the CIM 500. A.1 How to configure an IP address on your PC For connecting a PC to the CIM 500 via Ethernet, the PC must be set up to use a fixed (static) IP address belonging to the same...
Page 27
Enter password. Default: Grundfos. User name and password can be changed on the Note web server under "Grundfos Management" A.4 PROFINET IO configuration This web page is used to configure all the parameters relevant to the PROFINET IO protocol standard. All settings can also be configured from a standard PROFINET IO configuration tool, for instance Siemens Primary Setup Tool (PST).
Page 29
GRUNDFOS Pumps (Hong Kong) Ltd. Turkey Norway BOMBAS GRUNDFOS DO BRASIL Unit 1, Ground floor GRUNDFOS POMPA San. ve Tic. Ltd. Sti. Av. Humberto de Alencar Castelo Branco, Siu Wai Industrial Centre GRUNDFOS Pumper A/S Gebze Organize Sanayi Bölgesi 29-33 Wing Hong Street &...