6. PROFINET IO, CIM 500 setup

6.1 Connecting the ethernet cable

WARNING
Electric shock
Death or serious personal injury
- Connect CIM 500 only to SELV or SELV-E circuits.
Use RJ45 plugs and ethernet cable. Connect the cable shield to
protective earth at both ends.
It is important to connect the cable shield to earth
through an earth clamp or to connect the cable shield
to earth in the connector.
CIM 500 is designed for flexible network installation; the built-in
two port switch makes it possible to daisy chain from product to
product without the need of additional ethernet switches. The last
product in the chain is only connected to one of the ethernet
ports. Each ethernet port has its own MAC address.
Ethernet
switch
CIM 500
CIM 500
Fig. 13 Example of Industrial Ethernet network
2
1
4
5
6
Fig. 14 Example of an ethernet connection, CIM 500
Pos.
Description
1
Industrial Ethernet RJ45 connector 1
2
Industrial Ethernet RJ45 connector 2
3
Rotary switch for protocol selection
4
Data activity LED for connector 1
5
Link LED for connector 1
6
Data activity LED for connector 2
7
Link LED for connector 2
Green and red status LED for ethernet
8
communication
Green and red status LED for internal
9
communication between the module and
the pump.
CIM 500
CIM 500
3
8
7
9
Designation
ETH1
ETH2
SW1
DATA1
LINK1
DATA2
LINK2
LED 1
LED 2
Pumpland.ru

6.2 Setting the Industrial Ethernet protocol

The CIM 500 ethernet module has a rotary switch for selection of
the Industrial Ethernet protocol. See fig. 15.
Fig. 15 Selecting the Industrial Ethernet protocol
Pos.
Description
0
PROFINET IO (default)
1
Modbus TCP
2
BACnet IP
3
EtherNet/IP
4
GRM IP (requires a contract with Grundfos)
Reserved, LED1 will be permanently red to indicate an
5..E
invalid configuration
Reset to factory default
Note: The rotary switch must be set in this position for
F
20 seconds before CIM 500 resets to factory default.
During this period LED1 flashes red and green at the
same time to indicate that a reset will occur.
Every change of the rotary switch while the module is
powered on will cause the module to restart.

6.3 Setting the IP addresses

The CIM 500 ethernet module is default set to a fixed IP address.
It is possible to change the IP address settings from the built-in
webserver.
Default IP settings
IP address:
used by the
Subnet mask: 255.255.255.0
webserver
Gateway:
IP settings for
Make the settings via the webserver
Modbus TCP
Device name and IP
Static configuration from the webserver
settings for
or configuration from the PROFINET IO
PROFINET IO
configuration tool.
192.168.1.100
192.168.1.1
9