7.8 Measurement modules

This is measurement data that can be read in Hydro MPC,
Control MPC and Hydro Multi-E.
PROFIBUS/PROFINET direction: Inputs.
Module Name
3
WarningCode
4
FaultCode
5
VolumeFlow
6
Head
7
RemotePressure
8
InletPressure
9
OutletPressure
10
Level
11
FeedTankLevel
12
Power
13
Energy
14
RemoteTemperature
15
AmbientTemperature
16
InletTemp
17
OutletTemp
18
TemperatureDifference
19
OperationTime
20
ActualSetpoint
21
RelativePerformance
18
Data
Unit
Description
type
The Grundfos-specific warning code.
5
-
For a list of warning codes. See section
warnings.
The Grundfos-specific alarm code.
5
-
For a list of alarm codes. See section
warnings.
Provides the flow through the system as estimated or
3
8
m
/h
measured.
Provides the differential pressure between inlet and outlet
8
bar
as estimated, or measured, by the booster system.
Provides the measured pressure at an external pressure
8
bar
sensor. This pressure sensor must be installed for this
value to be valid.
Provides the inlet pressure if a pressure sensor is
8
bar
configured and installed at the inlet.
It has an offset of -1.000 bar.
Provides the outlet pressure measured by a pressure
8
bar
sensor.
Provides the tank level.
8
m
Requires that a level sensor is installed.
It has an offset of -100 metres.
Provides the feed tank level.
8
m
Requires that a level sensor is installed.
It has an offset of -100 metres.
Provides the actual power consumed by the booster
8
W
system.
Provides the accumulated electric energy consumption of
8
Wh
the system.
Provides the temperature measured by a remote
8
°C
temperature sensor.
Provides the ambient temperature measured by a
8
°C
temperature sensor.
Provides the inlet temperature measured by a temperature
8
°C
sensor.
Provides the outlet temperature measured by a
8
°C
temperature sensor.
8
°C
Provides the differential temperature.
8
h
Provides the total operating hours of the booster system.
Selected system control-loop setpoint.
8
%
See description of scaling for a setpoint in
module (ControlModule, module 2)
Value of speed control signal to pumps that are not
8
%
stopped or running at maximum speed.