Zone Pump Extension Modules; (Zonepump#Extmodule, Modules 35 To 40); Pilot Pump Module (Pilotpumpmodule, Module 55); Backup Pump Module (Backuppumpmodule, Module 56) - Grundfos CIM 150 PROFIBUS DP Functional Profile And User Manual

Profibus and profinet for grundfos boosters
Hide thumbs Also See for CIM 150 PROFIBUS DP:
Table of Contents

Advertisement

7.10 Zone pump extension modules

(ZonePump#ExtModule, modules 35 to 40)

A zone pump extension module is only available for Hydro/
Control MPC-E, Multi-E/TPED model H and MAGNA3-D. Its data
type is 10, non-standard.
Byte
Name
Bytes 1 to 4
Current [A]
(data type 8)
Bytes 5 to 8
Power [W]
(data type 8)
Byte 9
MotorTemperature
(data type 5)
[°C]
Byte 10
ControlSource
(data type 5)
[enum]
7.11 Pilot pump module (PilotPumpModule, module
55)
This module is available for CU 352 only.
A pilot pump module is only available for Hydro MPC-E and only if
the pilot pump is an E-pump.
Byte
Name
FaultCode
1
[enum]
Speed
2-3
[0.01 %]
Power
4-5
[1 W]
7.12 Backup pump module (BackupPumpModule,
module 56)
This module is available for CU 352 only.
A backup pump module is only available for Hydro MPC-E and
only if the backup pump is an E-pump.
Byte
Name
FaultCode
1
[enum]
Speed
2-3
[0.01 %]
Power
4-5
[1 W]
Description
Zone pump motor current.
Zone pump motor power.
Zone pump motor
temperature.
Zone pump control source:
1: Buttons on pump
2: GENIbus (booster
system)
3: GENIlink (Grundfos GO
Remote)
4: External digital control.
Description
Fault code, pilot pump.
Relative speed, pilot
pump.
Power consumption, pilot
pump.
Description
Fault code, backup pump.
Relative speed, backup
pump.
Power consumption,
backup pump.
Pumpland.ru
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents