Grundfos CIM 150 PROFIBUS DP Functional Profile And User Manual page 20

Profibus and profinet for grundfos boosters
Hide thumbs Also See for CIM 150 PROFIBUS DP:
Table of Contents

Advertisement

Module Name
28
PumpsCommFault
41
UserSetpoint
42
AnalogueInfluence
43
NoOfPowerOn
44
FeedBackSensorUnit
45
FeedbackSensorMin
46
FeedbackSensorMax
51
AutoModePumps
52
FlowMeasurement1
53
FlowMeasurement2
53
FlowMeasurement2
58
SelectedFeedbackSensor
S:
Sensor required.
●:
Always available.
●*:
Hydro Multi-E model G only.
For Hydro/Control MPC, see the table below.
●**: MPC-E only.
●***: CU 352 only.
20
Data
Unit
Description
type
One bit for each pump indicating that there is no
communication with the pump.
Logical "1": No communication with the pump.
0: Communication fault, zone pump 1
1: Communication fault, zone pump 2
5
Bits
2: Communication fault, zone pump 3
3: Communication fault, zone pump 4
4: Communication fault, zone pump 5
5: Communication fault, zone pump 6
6: Communication fault, pilot pump
7: Communication fault, backup pump.
User setpoint as written from the bus or selected on the
booster.
8
%
See description of scaling for a setpoint in
module (ControlModule, module
8
%
Influence from analog input.
8
-
Number of power-on cycles.
Scaling unit for the closed-loop feedback sensor
0: bar
7:
1: mbar
8:
2: m
9:
5
Enum
3: kPa
10: °C
4: psi
11: °F
5: ft
12: %
3
6: m
/h
13: m
Sensor
6
Minimum value for the closed-loop feedback sensor.
unit
Sensor
6
Maximum value for the closed-loop feedback sensor.
unit
One bit for each pump indicating if the pump is
commanded to stop from PROFIBUS/PROFINET or is in
auto mode, controlled from CU 352.
Logical "1": Pump in auto mode.
0: Zone pump 1 in auto mode
1: Zone pump 2 in auto mode
2: Zone pump 3 in auto mode
5
Bits
3: Zone pump 4 in auto mode
4: Zone pump 5 in auto mode
5: Zone pump 6 in auto mode
6: Pilot pump in auto mode
7: Backup pump in auto mode.
The data module ControlPumps (module 50) is used to
command the individual pumps.
3
6
0.1 m
/h Flow measurement 1 from sensor.
3
6
0.1 m
/h Flow measurement 2 from sensor.
3
6
0.1 m
/h Flow measurement 3 from sensor.
Read selected feedback sensor type
5
Enum
3: Flow sensor
6: Pressure sensor
Pumpland.ru
7.2 Control
2).
3
m
/s
14: l/h
l/s
15: l/min
gpm
16: gal/h
17: gal/s
3
18: ft
/h
3
19: ft
/min
3
3
/min
20: ft
/s
-
-
-
-
-
●*
-
-
-
●***
-
-
-
S
-
-
-
S
-
-
-
S
-
-
-
●***
-
-
-