English (GB) Installation and operating instructions 2. Applications Original installation and operating instructions The CIM 500 Ethernet module enables data CONTENTS transmission between an industrial Ethernet network Page and a Grundfos product. The module supports various industrial Ethernet Symbols used in this document protocols.
2.1 Abbreviations 2.2 CIM 500 Ethernet module APDU Application Protocol Data Unit Address Resolution Protocol. Translates IP addresses to MAC addresses. Ethernet cable type with four CAT5 twisted-pair cables. Enhanced CAT5 cable with better CAT5e performance. CAT6 Cable with very high performance.
3. Installation Warning Only connect the CIM 500 to SELV or SELV-E circuits. 3.1 Connecting the Ethernet cable Use RJ45 plugs and Ethernet cable. Connect the cable screen to protective earth at both ends. It is important to connect the cable screen...
To establish a connection from a The module has a rotary switch for selection of the PC to the CIM 500, proceed as follows: industrial Ethernet protocol. See fig. 4. 1. Connect the PC and the module, using an Ethernet cable.
GRM server. Permanently Product not supported. See Resetting to factory settings. section 6.2 PROFINET Flashing red After 20 sec. the CIM 500 will and green Permanently Error in firmware download. See restart. red and green section 6.2 PROFINET LED1, Modbus TCP/BACnet IP Resetting to factory settings.
5. Data activity and link LEDs The module has two connectivity LEDs related to each RJ45 connector. See fig. 1. DATA1 and DATA2 These yellow LEDs indicate data traffic activity. Status Description No data communication on RJ45 connector Data communication on RJ45 Flashing connector Heavy network traffic...
6. Fault finding 6.1 Modbus TCP/BACnet IP You can detect faults in a module by observing the status of the two status LEDs. See the tables below. CIM 500 fitted in a Grundfos product Fault (LED status) Possible cause Remedy...
Page 10
CIM 500 fitted in a CIU 500 Fault (LED status) Possible cause Remedy Both LEDs remain off when The CIU 500 is defective. the power supply is Replace the CIU 500. connected. LED2 is flashing red. No internal communication • Check the cable connection...
6.2 PROFINET IO CIM 500 fitted in a Grundfos product Fault (LED status) Possible cause Remedy Both LEDs remain off when The module is fitted Check that the module is the power supply is incorrectly in the Grundfos fitted/connected correctly.
Page 12
CIM 500 fitted in a CIU 500 Fault (LED status) Possible cause Remedy Both LEDs remain off when The CIU 500 is defective. the power supply is Replace the CIU 500. connected. LED1 remains off. SW1 is set to "1".
6.3 GRM IP CIM 500 fitted in a Grundfos product Fault (LED status) Possible cause Remedy Both LEDs remain off when the power The module is fitted Check that the module is supply is connected. incorrectly in the Grundfos fitted/connected correctly.
CIM 500 fitted in a CIU 500 (FOR GRM) Fault (LED status) Possible cause Remedy Both LEDs remain off when The CIU 500 is defective. the power supply is Replace the CIU 500. connected. LED1 remains off. SW1 is set to "1".
Page 15
By means of the web server you can also update the firmware of the CIM 500 module and store/restore settings. To connect a PC to the CIM 500, proceed as follows: 1. Connect the PC and the module, using an Ethernet cable.
Page 16
Object Description Enter username. Default: admin. Username You can change the username via the User Management web page. See page 138. Enter password. Default: Grundfos. Password You can change the password via the User Management web page. See page 138.
Page 17
Modbus TCP configuration Fig. 3 Real Time Ethernet Protocol Configuration - Modbus TCP Object Description The default value is 502, the official IANA-assigned Modbus TCP port number. The number 502 will always be active implicitly. TCP Port Number If you select another value in the web server configuration field, both the new value and value 502 will be active.
Page 18
Select Device Instance. The default number is 22700. The Device Instance must be Device Instance unique in the BACnet network. Grundfos is 227 and it is fixed. The lasts three digits can be changed. You can name the device. The device name must be unique in the BACnet network Device Name (optional).
Page 19
PROFINET IO master to a module fitted in a CIU or an E-box without installing this device in a real industrial process system. In an office environment, it can then be Grundfos product verified that communication works and data are received and handled correctly by the simulation PROFINET IO master application program (e.g.
Page 20
Real time ethernet protocol configuration Object Description GRMIP port A change is only needed in case Grundfos requires it number The default URL link to the GRM Server is active but hidden. A change is only needed in case Grundfos requires it.
Page 21
Network settings Fig. 7 Network settings Object Description IP address Factory setting: 192.168.1.100. Subnet mask Factory setting: 255.255.255.0. Gateway Factory setting: 192.168.1.1. The module can be configured to use a specific domain name server. DNS Server Factory setting: 0.0.0.0. The module can be configured to automatically obtain the IP address from a DHCP Use DHCP server on the network.
Page 22
GENIpro TCP port settings TCP Port Number The module can transfer data from a Grundfos PC tool to the product via the GENIpro protocol. Fig. 8 GENIpro TCP port settings Object Description The TCP port number of the module and that of the PC tool must be identical.
Page 23
Email Configuration The web server in the module can be set to send an email notification in case of internal module events. Fig. 9 Email Configuration Object Description Enter the IP address of the SMTP server. If you enter a URL, the module will look it up SMTP Server via a DNS server and replace it with the IP address.
Page 24
Time Configuration Object Description Enter the IP address of the SNTP server and the CIM 500 will automatically adjust its clock. If you do not configure the SNTP server, or the connection is lost, the module will SNTP Server use the internal clock. If you enter a URL, the module will look it up via a DNS server and replace it with the IP address.
Page 25
User Management You must log in to use the built-in web server for configuration. The usernames and passwords can be configured from this page. The web server operates with two types of user: Administration – Access to all configurations/functions. Configuration which gives access to: –...
Page 26
Update You can update the firmware by means of the built-in web server. The binary file is supplied by Grundfos. Configuration To make installation and configuration easier, you can upload the configuration to a PC for backup or distribution to multiple modules.
Page 27
My firma Grundfos prohlašujeme na svou plnou odpovědnost, že Wir, Grundfos, erklären in alleiniger Verantwortung, dass das Produkt výrobek CIM 500, na který se toto prohlášení vztahuje, je v souladu s CIM 500, auf das sich diese Erklärung bezieht, mit den folgenden níže uvedenými ustanoveními směrnice Rady pro sblížení...
Page 28
Chúng tôi, Grundfos, tuyên bố trong phạm vi trách nhiệm duy nhất Ne, Grundfos, deklarojmë vetëm nën përgjegjësinë tonë se produkti của mình rằng sản phẩm CIM 500 mà tuyên bố dưới đây có liên quan CIM 500, me të cilin ka lidhje kjo deklaratë, është në pajtim me tuân thủ...
Page 29
Argentina China Hong Kong Bombas GRUNDFOS de Argentina S.A. GRUNDFOS Pumps (Shanghai) Co. Ltd. GRUNDFOS Pumps (Hong Kong) Ltd. Ruta Panamericana km. 37.500 Centro 10F The Hub, No. 33 Suhong Road Unit 1, Ground floor Industrial Garin Minhang District Siu Wai Industrial Centre 1619 Garín Pcia.
Page 30
Malaysia Serbia Turkey GRUNDFOS Pumps Sdn. Bhd. Grundfos Srbija d.o.o. GRUNDFOS POMPA San. ve Tic. Ltd. 7 Jalan Peguam U1/25 Omladinskih brigada 90b Sti. Glenmarie Industrial Park 11070 Novi Beograd Gebze Organize Sanayi Bölgesi 40150 Shah Alam Phone: +381 11 2258 740...
Need help?
Do you have a question about the CIM 500 and is the answer not in the manual?
Questions and answers