Mounting on a support system
ATTENTION
50 | EN
6 3 2

Mounting an external corner

The external corner is used to change a duct route at a 90° angle from
the horizontal to the vertical. The lock plate suspended from threaded
rods (BSKM-GA 0407, BSKM-GA 0711 or BSKM-GA 1025) is used as
a support element for the duct sections. Together with the screwed-on
external corner (BSKM-AE 0407, BSKM-AE 0711 or BSKM-AE 1025), it
ensures the necessary tightness.
See Fig. 53:
1
Stick the self-adhesive sealing strip to the lock plate.
2
Fasten the threaded rods to the ceiling and fasten the lock plate to
the threaded rods with washers and nuts at the desired height.
3
Shorten the ducts as necessary and then re-drill the duct fastening
holes (see Fig. 12 on page 18). If necessary, use locking brackets
for the duct lid (see "4.4 Inserting locking brackets" on page 19).
Remove the duct lid and fix the duct sections with two self-tapping
screws each (contained in the scope of delivery of the lock plate) on
or to the lock plate.
Comply with the minimum bending radii of the cables!
Cables can be damaged on bending. When laying the cables in the ex-
ternal corner, ensure that the minimum bending radius, prescribed by the
cable manufacturer, is observed.
4
Insert cables.
5
For duct BSKM 1025: insert lid support (see "4.5 Using lid support"
on page 20).
6
Attach the duct lid firmly.
7
Attach the external corner and screw on with the supplied nuts.
8
Using connecting screws (contained in the scope of delivery of the
external corner), create the equipotential bonding (see "8.1 Create
equipotential bonding" on page 72).