OBO Bettermann PYROLINE Rapid Mounting Instructions page 24

Fire protection duct
Table of Contents

Advertisement

Direct mounting on the ceiling, wall or floor
BSKM 0407
100
200
400
24 | EN
100
100
400
400
Fig 20: Hole pattern for ceiling mounting, BSKM 0407
Apply the drill holes to the ceiling.
Drill the ceiling holes. For the fire protection bolt ties MMS-plus 7.5x50,
ensure a drilling depth of at least 65 mm, Ø 6 mm (see Fig. 11 on page
17).
Clean the drill holes carefully, e.g. through suction or blowing-out.
Fasten the duct to the two outermost holes and, at first, hand-tighten
the screws.
Fix the duct to the inner holes together with cable clamps for ceiling
mounting (BSKM-BD 0711 or BSKM-BD 1025) (see Fig. 16 on page
23).
Slacken the external fastenings, push in the cable clamps and screw
them tight, together with the duct.
Insert the cables in the cable clamps.
Push the duct lid on firmly.
Attach the connector (see "5.4 Connecting joints" on page 28) or
fitting (see "5.6 Mounting fittings" on page 31) and mark the drill
holes.
Remove the connector or fitting and drill the holes.
Attach the connector or fitting again and screw it on so that the joints
of the ducts are sealed evenly and securely.
Create the equipotential bonding (see "8.1 Create equipotential bond-
ing" on page 72).
100
100
400
200
200
400