Mounting An Internal Corner - OBO Bettermann PYROLINE Rapid Mounting Instructions

Fire protection duct
Table of Contents

Advertisement

Mounting on a support system
ATTENTION
52 | EN
6 3 3

Mounting an internal corner

The internal corner is used to change a duct route at a 90° angle from the
horizontal to the vertical. The lock plate suspended from threaded rods
(BSKM-GI 0407, BSKM-GI 0711 or BSKM-GI 1025) is used as a support
element for the duct sections. Together with the screwed-on internal
corner (BSKM-IE 0407, BSKM-IE 0711 or BSKM-IE 1025), it ensures the
necessary tightness.
See Fig. 54:
1
Stick the self-adhesive sealing strip to the lock plate.
2
Fasten the threaded rods to the ceiling and fasten the lock plate to
the threaded rods with washers and nuts at the desired height.
3
Shorten the ducts as necessary and then re-drill the duct fastening
holes (see Fig. 12 on page 18). If necessary, use locking brackets
for the duct lid (see "4.4 Inserting locking brackets" on page 19).
Remove the duct lid and fix the duct sections with two self-tapping
screws each (contained in the scope of delivery of the lock plate) on
or to the lock plate.
Comply with the minimum bending radii of the cables!
Cables can be damaged on bending. When laying the cables in the in-
ternal corner, ensure that the minimum bending radius, prescribed by the
cable manufacturer, is observed.
4
Insert cables.
5
For duct BSKM 1025: insert lid support (see "4.5 Using lid support"
on page 20).
6
Attach the duct lid firmly.
7
Attach the internal corner and screw on with the supplied nuts.
8
Using connecting screws (contained in the scope of delivery of the
internal corner), create the equipotential bonding (see "8.1 Create
equipotential bonding" on page 72).
OBO Bettermann

Advertisement

Table of Contents
loading

Table of Contents