Direct mounting on the ceiling, wall or floor
36 | EN
5 6 6

Mounting a reducer

The reducer can be used to create a reduction from the main duct to a
narrower duct. The following reductions are possible:
– 250 mm-wide duct routing (BSKM 1025) to a duct section of width
110 mm (BSKM 0711)
– 110 mm-wide duct routing (BSKM 0711) to a duct section of width
70 mm (BSKM 0407)
Mount the reducer as shown in Fig. 38.
Attach the reducer and fix it, e.g. with four fire protection bolt ties (see
"4.1 Fastening material" on page 17).
BSKM-RE 1025
BSKM-RE 0711
Fig 38: Mounting a reducer
5 6 7

Mounting a wall/ceiling penetration

With wall or ceiling penetrations, for the achievement of the fire resist-
ance class I30–I90, it is sufficient to plug the cavities around the duct with
mineral wool and seal them with filler (see "5.5 Creating a wall/ceiling
penetration" on page 29).
However, if I120 is to be achieved, then seal both sides of the penetration
with a wall connection fitting BSKM-WA 0711 or BSKM-WA 1025 (see Fig.
39). The overlapping ensures the necessary tightness. The wall connec-
tion fitting is only available for BSKM 0711 and BSKM 1025.
The mounting example shows a wall penetration. The ceiling penetration
is mounted in essentially the same way.
BSKM 0711
BSKM 0407
BSKM 1025
BSKM 0711