Creating A Rear-Side Cable Outlet - OBO Bettermann PYROLINE Rapid Mounting Instructions

Fire protection duct
Table of Contents

Advertisement

Mounting instructions PYROLINE
7 3

Creating a rear-side cable outlet

With ducts that are fastened on the rear side to a solid wall or ceiling, you
can create a round opening on the rear side and use it as a cable outlet
(see Fig. 68).
The maximum opening diameter for BSKM 0711 and BSKM 1025 is
80 mm and 40 mm for BSKM 0407.
Create an opening on the rear side of the duct, e.g. with a step drill.
Carefully de-burr the edges.
Run the core drill hole through the masonry.
Pass the cables through.
Completely close the opening with a suitable fire protection filler. We
recommend the OBO system PYROPLUG
PYROPLUG
Ø max. 80 mm for BSKM 0711/1025
Ø max. 40 mm for BSKM 0407
Fig 68: Rear side cable outlet
Rapid fire protection duct
®
Screed, type FBA-SP).
®
Creating cable outlets
Mini (1-component filler
®
EN | 71