Huawei ECC800-Pro User Manual page 287

Data center controller
Hide thumbs Also See for ECC800-Pro:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
2.
3.
Step 2 Add a PDU8000 (Modbus-RTU).
1.
2.
Issue 02 (2020-09-07)
Choose System Info > Settings, enter the user name admin and password
000001, and tap
password, tap Confirm.
Tap Communication and check IP address assign to Manual. And set Serial
port baud rate to 9600, and Serial port address to 1 on the displayed
communication settings screen.
Figure 8-11 PDU8000 communication settings screen
Log in to the ECC800-Pro WebUI as an administrator.
Add a PDU8000.
Table 8-12 Adding a PDU8000
Path
Parameter
Choose
Device
System
attribute
Settings >
Device Type
Device
Management
and click Add
Connect To
Device. The
parameters
for adding
Communicati
devices are
ons Port
displayed.
Copyright © Huawei Technologies Co., Ltd.
. In the displayed dialog box for confirming the
Setting
Select PDU from the drop-down list box.
Select PDU8000 from the drop-down list
box.
Select ECC800 from the drop-down list
box.
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the
PDU8000 is connected to the COM1 port on the
ECC800-Pro. If the PDU8000 is connected to
another port, enter the number of the
connected port.
8 FAQ
276