ECC800 Data Center Controller
User Manual (for ECC800-Pro)
●
Step 5 (Optional) Click Add, set IT Cabinet, select a UIM and the devices connected to
each COM port of the UIM20A, and click
manually bind the devices.
Step 6 Click Submit.
Step 7 Hold down the BLINK button on the UIM for less than 2s. The RUN indicator on
the UIM blinks fast, and the dialog box for binding IT cabinets and devices shows
the UIM that is blinking.
Issue 02 (2020-09-07)
Connected
Cabinet 1
Cabinet
Temperature map scenario
In the scenario where T/H sensors are connected, 32 T/H sensors are
connected to one UIM.
NO TE
– Each COM port allows a maximum of eight T/H sensors to be cascaded.
– The addresses of the T/H sensors connected to the same COM port must be
different. Addresses 1 to 8 are supported. The addresses of T/H sensors connected
to different COM ports can be the same. In actual configuration, bind sensors to
the corresponding cabinets in sequence.
– Each cabinet can connect to only one T/H sensor, a T/H sensor is automatically
bound to the cabinet after its DIP switch is set. The LCD of the T/H sensor displays
the DIP switch address.
– One UIM connects to 32 T/H sensors. If the smart module connects to more than
32 IT cabinets, two UIMs are required for expansion. Each UIM must be installed in
the first cabinet of the corresponding IT cabinets, and the cable connection
principles remain unchanged.
– In this scenario, a UIM is not bound to the IT cabinet.
– Only the T/H sensor inside the cabinet can be connected to the UIM.
Table 6-3 Cable connection mode in a temperature map scenario
COM Port
COM1
Connected
T/H sensor
Device
group
COM Port
COM2
Connected
N/A
Device
NO TE
If the automatic cabinet binding result is inconsistent with the actual connection or the
automatic cabinet binding function cannot be used, you need to manually bind devices.
NO TE
You can determine the IT cabinet that houses the UIM through indicator blinking. Then, you
can change the IT cabinet name.
Copyright © Huawei Technologies Co., Ltd.
Cabinet 2
Cabinet 3
COM3
COM5
T/H sensor
T/H sensor
group
group
COM4
COM6
N/A
N/A
in the Operation column to
6 Feature Description
Cabinet 4
COM7
T/H sensor
group
COM8
N/A
130