Querying The U Space Use Information; Commissioning The Smart U Space Manager (Connected To A Uim20A Expansion Module); Determining The Position Of The Smart U Space Manager - Huawei ECC800-Pro User Manual

Data center controller
Hide thumbs Also See for ECC800-Pro:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 View the position of the smart U space manager.
1.
2.
----End

6.10.1.2 Querying the U Space Use Information

Prerequisites
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose Home > Plan View to access the Plan View page, where you can create
or modify the views of the smart module. Drag the icon of a registered device or
device in the cabinet list to the planned position to generate the plan view.
Step 3 Choose Monitoring > Cabinet > IT Cabinet n > Smart U Space Manager1, check
U space quantity, U Space Information and so on.
----End
6.10.2 Commissioning the Smart U Space Manager
(Connected to a UIM20A Expansion Module)

6.10.2.1 Determining the Position of the Smart U Space Manager

If a smart U space manager is installed, perform the following steps to configure
it.
Issue 02 (2020-09-07)
Choose Monitoring > Cabinet > IT Cabinet > Smart U Space Manager.
Select Running Control and click Blink. In the actual environment, you will
see that the smart U space manager blinks to ensure that the device location
in the view is consistent with that in the smart module.
Figure 6-70 Viewing the position of the smart U space manager
The ECC800-Pro is connected to the NMS that supports asset management.
The actual assets of the smart module have been allocated.
Copyright © Huawei Technologies Co., Ltd.