Connecting Probe/Sensor Wiring to Consoles
PUMP SENSE MODULE - POWER BAY
Connect the two color-coded or marked wires from the pump controls to the appropriate terminals on the Pump
Sense Module [see Figure 69].
PUMP
PUMP
CONTROL
CONTROL
#1
#1
WIRING ADDITIONAL POWER BAY MODULES
The wiring diagrams for Power Bay modules not covered in this manual can be found in the separate Veeder-Root
manuals listed below. Follow the instructions in the manual shipped with the module.
Module
Pressure Line Leak Controller Modules
Line Leak Interface Module
WPLLD Controller Module
WPLLD AC Interface Module
Mechanical Dispenser Interface Module
1
PUMP
PI PR PI PR PI PR PI PR
PUMP SENSE MODULE
Pump In
Pump Return
PUMP
PUMP
Pump In
CONTROL
CONTROL
Pump Return
#2
#2
Required with Pressure Line Leak Detection.
Required with Volumetric Line Leak Detection.
Required with Wireless Pressurized Line Leak
Detection.
Required with Wireless Pressurized Line Leak
Detection.
Consoles w/BIR only - Dispensing system input
from mechanical dispensers. Accepts inputs
from up to 4 pulsers or pulse/totalizers.
2
3
4
Up to 4
Rigid Conduit (enters
Pump
Console through a
Controls
Power Bay knockout)
Description
71
TLS-350/ProMax/EMC Consoles
INPUT RATING
120 VAC
.15 AMP MAX
Console
consoles\psmw.eps
Figure 69. Pump Sense Module Wiring
Manual No.
576013-499
576013-765
577013-481
577013-481
576013-893