6/54
1

Safety rules

Save these instructions!
This manual contains important instructions for models MegaFlex 1000 to 1600 that should be followed during
installation and maintenance of the UPS and Battery.
General
-
Move the UPS in an upright position in its original package to the final destination room.
To lift the cabinets, use a forklift or lifting belts with spreader bars.
-
Check for sufficient floor and elevator loading capacity.
-
Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS.
Contact your ABB Service Center immediately.
-
WARNING! RISK OF ELECTRICAL SHOCK!
Do not remove covers, there are no user serviceable parts inside.
-
After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltage remains
at the terminals of the electrolytic capacitors.
-
UPS's and Battery system require a 12 months periodic maintenance to operate reliably and safely.
This should be performed by qualified service personnel. The UPS contains its own energy source (Battery).
-
The field-wiring outlets may be electrically live, even when the UPS is disconnected from the Utility.
-
Dangerous voltages may be present during Battery operation.
-
The Battery must be disconnected during maintenance or service work.
-
This UPS contains potentially hazardous voltages.
-
Be aware that the Inverter can restart automatically after the Utility voltage is restored.
-
End user must follow applicable regional occupational safety codes/regulations during installation, operation
and equipment maintenance. This may require additional field marking or labelling defining appropriate level
of PPE (Personal Protection Equipment) to reduce the risk of Arc-flash related injuries.
Contact our ABB Service Center for product specific information.
Installation
-
This UPS must be installed and connected only by trained personnel.
-
Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
-
After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are correctly
reattached.
-
This UPS is intended for use in a controlled indoor environment free of conductive contaminants and
protected against animals intrusion.
-
WARNING! HIGH LEAKAGE CURRENT TO GROUND:
Ground connection is essential before connecting to AC input!
-
Switching OFF the Unit does not isolate the UPS from the Utility.
-
Do not install the UPS in an excessively humid environment or near water.
-
Avoid spilling liquids on or dropping any foreign object into the UPS.
-
The Unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104°F
(40°C).
-
Optimal Battery life is obtained if the ambient temperature does not exceed 77°F (25°C).
-
It is important that air can move freely around and through the Unit. Do not block the air vents.
-
Avoid locations in direct sunlight or near heat sources.
Storage
-
Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (+55°C).
-
The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the range -4°F
(-20°C) to 104°F (40°C).
-
If the Unit is stored for a period exceeding 3 months, the Battery must be recharged periodically (time
depending on storage temperature).
Battery
-
The Battery-voltage is dangerous for person's safety.
-
When replacing the Battery, use the same number, voltage (V) and capacity (Ah).
-
Proper disposal or recycling of the Battery is required.
Refer to your local codes for disposal requirements.
-
Never dispose of Battery in a fire: they may explode.
-
Do not open or mutilate Battery: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
-
Avoid charging in a sealed container.
-
Never short-circuit the Batteries.
When working with Batteries, remove watches, rings or other metal objects and only use insulated tools.
-
In case of air shipment, the cables +/- going to the Battery fuses/terminals shall be disconnected and isolated.
MegaFlex 1000 to 1600
UPS Installation Guide / REV-A