Bus Bars Interconnection - ABB MegaFlex 1000 UL S1 Installation Manual

Hide thumbs Also See for MegaFlex 1000 UL S1:
Table of Contents

Advertisement

25/54

4.7.2 Bus bars interconnection

Note!
All the bus bars interconnection must be performed only by an ABB Service Technician!
MegaFlex 1000 to 1600 - Bus bars interconnection
L1
Inverter bus bars
(2x 80/5x397 mm)
Module not available in the
MegaFlex 1000 - 1100 - 1200
Power Section cabinet
Torque Specifications
Bolt size (mm): M8
Connection
L1 Inverter
L2 Inverter
L3 Inverter
L1 Rectifier
L2 Rectifier
L3 Rectifier
Battery +
Battery -
Rectifier bus bars (2x 80/5x310 mm)
L1
L2
L3
L3
L2
In/Out Section cabinet
Fig. 4.7.2-1 MegaFlex 1000 to 1600 – Bus bars interconnection
Bolt torque: 195 Lb-in / 22 N-m
Description of connection
Interconnection L1 Inverter
Interconnection L2 Inverter
Interconnection L3 Inverter
Interconnection L1 Rectifier
Interconnection L2 Rectifier
Interconnection L3 Rectifier
Interconnection Battery +
Interconnection Battery +-
MegaFlex 1000 to 1600
Detail showing bus bars interconnection
Rectifier and Inverter bus bars
Note!
These 2 bus bar of this module
not to be mounted in the
MegaFlex 1000 - 1100 - 1200
Bus bars interconnection
2 Bus bar 80/5 x 397 mm
2 Bus bar 80/5 x 397 mm
2 Bus bar 80/5 x 397 mm
2 Bus bar 80/5 x 310 mm
2 Bus bar 80/5 x 310 mm
2 Bus bar 80/5 x 310 mm
Bus bar 60/5 x 292 mm (1 for every module, total 4)
Bus bar 60/5 x 292 mm (1 for every module, total 4)
UPS Installation Guide / REV-A
Bolt M8x35
M8 spring washer
M8 flat washer
2 bus bars (removable)
2 bus bar (fixed)
Pre fixed nut M8
Battery bus bars
(60/5x292 mm)
-
+
Detail showing
bus bars interconnection
Battery bus bars
Pre fixed Nut M8
Bus bar (fixed)
Bus bar (removable)
M8 flat washer
M8 spring washer
Bolt M8x35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents