Specifications

8 Specifications

8.1 Power-Dependent Specifications

8.1.1 Mains Supply 3x380-480 V AC

Normal Overload =110% current for 60 s
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Typical shaft output at 480 V [kW]
Enclosure IP21/54
Output current
Continuous (at 400 V) [A]
Intermittent (60 s overload) (at 400 V) [A]
Continuous (at 460/480 V) [A]
Intermittent (60 s overload) (at 460/480 V)
[A]
8
8
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Continuous kVA (at 480 V) [kVA]
Max. Input current
Continuous (at 400 V) [A]
Continuous (at 460/480 V) [A]
Max. pre-fuses
1)
Max. cable size
2
Motor (mm
/AWG
Mains (mm
2
/AWG
2
Brake (mm
/AWG
Total LHD loss 400 V AC [kW]
Total back channel loss 400 V AC [kW]
Total filter loss 400 V AC [kW]
Total LHD loss 460 V AC [kW]
Total back channel loss 460 V AC [kW]
Total filter loss 460 V AC [kW]
Weight, enclosure IP21, IP54 [kg]
4)
Efficiency
Output frequency [Hz]
Heatsink overtemp. trip [°C]
Power card ambient trip [°C]
*High overload = 160% torque during 60 s; Normal overload = 110% torque during 60 s
Table 8.1 Mains Supply 3x380-480 V AC
72
Operating Instructions
[A]
2)
)
2)
)
2)
)
Danfoss A/S © Rev. 2014-07-29 All rights reserved.
P160
NO
160
250
200
D13
315
347
302
332
218
241
262
304
291
400
2x185 (2x300 mcm)
8868
7318
4954
9059
7123
5279
380
0.96
0-800
105
85
P200
P250
NO
NO
200
250
300
350
250
315
395
480
435
528
361
443
397
487
274
333
288
353
313
384
381
463
348
427
500
630
10527
11751
8903
10033
5714
6234
10192
11706
8209
9635
5819
6681
406
MG16I202

Advertisement

Table of Contents
loading

Table of Contents