Danfoss VLT HVAC Drive FC 102 Operating Instructions Manual page 63

Low harmonic drive
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Diagnostics and Troubleshoo...
Number
Text
1380
Option B did not respond when calculating the
platform version.
1381
Option C0 did not respond when calculating the
platform version.
1382
Option C1 did not respond when calculating the
platform version.
1536
An exception in the application-oriented control is
registered. The debug information is written on
the LCP.
1792
DSP Watch Dog is active. Debugging of power
part data, motor-oriented control data not
transferred correctly.
2049
Power data restarted.
2064–2072 H081x: Option in slot x has restarted.
2080–2088 H082x: Option in slot x has issued a power-up
wait.
2096–2104 H983x: Option in slot x has issued a legal power-
up wait.
2304
Could not read any data from the power EEPROM.
2305
Missing software version from the power unit.
2314
Missing power unit data from the power unit.
2315
Missing software version from the power unit.
2316
Missing lo_statepage from the power unit.
2324
The power card configuration is determined to be
incorrect at power-up.
2325
A power card has stopped communicating while
mains power is applied.
2326
The power card configuration is determined to be
incorrect after the delay for power cards to
register.
2327
Too many power card locations have been
registered as present.
2330
The power size information between the power
cards does not match.
2561
No communication from DSP to ATACD.
2562
No communication from ATACD to DSP (state
running).
2816
Stack overflow control board module
2817
Scheduler slow tasks
2818
Fast tasks
2819
Parameter thread
2820
LCP stack overflow
2821
Serial port overflow
2822
USB port overflow
2836
cfListMempool is too small.
3072–5122 The parameter value is outside its limits.
5123
Option in slot A: Hardware incompatible with the
control board hardware.
5124
Option in slot B: Hardware incompatible with the
control board hardware.
5125
Option in slot C0: Hardware incompatible with the
control board hardware.
5126
Option in slot C1: Hardware incompatible with the
control board hardware.
MG16I202
Operating Instructions
Number
5376–6231 Out of memory
Table 7.5 Internal Fault, Code Numbers
ALARM 39, Heat sink sensor
No feedback from the heat sink temperature sensor.
The signal from the IGBT thermal sensor is not available on
the power card. The problem could be on the power card,
on the gate drive card, or the ribbon cable between the
power card and gate drive card.
WARNING 40, Overload of digital output terminal 27
Check the load connected to terminal 27 or remove the
short-circuit connection. Check 5-00 Digital I/O Mode and
5-01 Terminal 27 Mode.
WARNING 41, Overload of digital output terminal 29
Check the load connected to terminal 29 or remove the
short-circuit connection. Check 5-00 Digital I/O Mode and
5-02 Terminal 29 Mode.
WARNING 42, Overload of digital output on X30/6 or
overload of digital output on X30/7
For X30/6, check the load connected to X30/6 or remove
the short-circuit connection. Check 5-32 Term X30/6 Digi
Out (MCB 101).
For X30/7, check the load connected to X30/7 or remove
the short-circuit connection. Check 5-33 Term X30/7 Digi
Out (MCB 101).
ALARM 45, Earth fault 2
Ground fault.
Troubleshooting
ALARM 46, Power card supply
The supply on the power card is out of range.
There are 3 power supplies generated by the switch mode
power supply (SMPS) on the power card: 24 V, 5 V, and±18
V. When powered with 24 V DC with the MCB 107 option,
only the 24 V and 5 V supplies are monitored. When
powered with 3-phase mains voltage, all 3 supplies are
monitored.
WARNING 47, 24 V supply low
The 24 V DC is measured on the control card. This alarm
appears when the detected voltage of terminal 12 is <18
V.
Troubleshooting
Danfoss A/S © Rev. 2014-07-29 All rights reserved.
Text
Check for proper grounding and loose
connections.
Check for proper wire size.
Check the motor cables for short circuits or
leakage currents.
Check for a defective control card.
7
7
61

Advertisement

Table of Contents
loading

Table of Contents