Application Examples
6.2.4 RS-485
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
RS-485
06
61
+
68
69
-
Table 6.9 RS-485 Network Connection
MG16I202
Operating Instructions
Parameters
Function
Setting
8-30 Protocol
FC*
8-31 Address
1*
8-32 Baud Rate
9600*
* = Default Value
Notes/comments:
Select protocol, address and
baud rate in the above
mentioned parameters.
D IN 37 is an option.
Danfoss A/S © Rev. 2014-07-29 All rights reserved.
6.2.5 Motor Thermistor
WARNING
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
Use only thermistors with reinforced or double
insulation to meet PELV insulation
requirements.
VLT
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 6.10 Motor Thermistor
Parameters
Function
Setting
1-90 Motor
[2]
Thermal
Thermistor
Protection
trip
1-93 Thermistor
[1] Analog
Source
input 53
* = Default Value
Notes/comments:
If only a warning is desired,
parameter 1-90 Motor Thermal
Protection should be set to [1]
Thermistor warning.
D IN 37 is an option.