Commissioning
Inspect for
Description
Grounding
The unit requires a ground wire from its chassis to the building ground.
Check for good ground connections that are tight and free of oxidation.
Grounding to conduit or mounting the back panel to a metal surface is not sufficient.
Input and output power
Check for loose connections.
wiring
Check that motor and mains are in separate conduit or separated screened cables.
Panel interior
Inspect that the unit interior is free of debris and corrosion.
Switches
Ensure that all switch and disconnect settings are in the proper positions.
Vibration
Check that the unit is mounted solidly or that shock mounts are used, as necessary.
Check for an unusual amount of vibration.
Table 5.1 Start-up Checklist

5.2 Applying Power

WARNING
HIGH VOLTAGE!
Frequency converters contain high voltage when
connected to AC mains. Installation, start-up and
maintenance should be performed by qualified
personnel only. Failure to comply could result in death
or serious injury.
WARNING
UNINTENDED START!
When the frequency converter is connected to AC mains,
the motor may start at any time. The frequency
converter, motor, and any driven equipment must be in
operational readiness. Failure to comply could result in
death, serious injury, equipment, or property damage.
1.
Confirm that the input voltage is balanced within
3%. If not, correct input voltage imbalance before
proceeding.
2.
Ensure that optional equipment wiring, if present,
matches the installation application.
3.
Ensure that all operator devices are off. Panel
doors should be closed or cover mounted.
4.
Apply power to the unit. Do not start the
frequency converter at this time. For units with a
disconnect switch, turn the switch on to apply
power.
NOTICE
If the status line at the bottom of the LCP reads AUTO
REMOTE COASTING or Alarm 60 External Interlock is
displayed, this indicates that the unit is ready to operate
but is missing an input signal on terminal 27.
MG16I202
Operating Instructions

5.3 Local Control Panel Operation

5.3.1 Local Control Panel

The local control panel (LCP) is the combined display and
keypad on the front of the unit.
The LCP has several user functions:
An optional numeric LCP (NLCP) is also available. The NLCP
operates in a manner similar to the LCP. See the product
relevant programming guide for details on use of the NLCP.
NOTICE
For commissioning via PC, install the MCT 10 Set-up
Software. The software is available for download (basic
version) or for ordering (advanced version, order number
130B1000). For more information and downloads, see
www.danfoss.com/BusinessAreas/DrivesSolutions/Software
+MCT10/MCT10+Downloads.htm.

5.3.2 LCP Layout

The LCP is divided into 4 functional groups (see
Illustration 5.1).
Danfoss A/S © Rev. 2014-07-29 All rights reserved.
Start, stop, and control speed when in local
control.
Display operational data, status, warnings and
cautions.
Programme frequency converter functions.
Manually reset the frequency converter after a
fault when auto-reset is inactive.
A. Display area
B. Display menu keys
C. Navigation keys and indicator lights (LEDs)
D. Operation keys and reset
5
5
43