If the temperature of the cooling liquid is chosen to be lower than the ambient
temperature, there is a risk of condensation.
When used and stored in a frost-prone area, corrosion protection (e.g. Clariant) has to
be added.

4.1.2 Determination of water flow Q

Example
Pv:
450 W
∆T_Water: 4 °C
-> Q_Water:
1.6 l / min
To achieve a very regular cooling of the motor, the max. difference between flow and return
temperature should not exceed 10 ° C.
NTI AG / LinMot
P10-70-SSC / P10-70-SSC-D02
ENG
Page 15 / 32