750-653 (/xxx-xxx) [Serial Interface RS 485]

Technical Data

2.1.1.6
Technical Data
Module Specific Data
Transmission channel
Baud rate
Bit transfer
Transmission length
Buffer
Current consumption (internal)
Voltage supply
Isolation
Bit width
Dimensions (mm) W x H x L
Weight
Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual)
EMC-Immunity to interference (CE)
EMC-Emission of interference (CE)
Approvals (cf. Chapter 2.2 of the Coupler/Controller Manual)
UL
(UL508)
C
US
ABS (American Bureau of Shipping)
BV (Bureau Veritas)
DNV (Det Norske Veritas)
GL (Germanischer Lloyd)
KR (Korean Register of Shipping)
LR (Lloyd's Register)
NKK (Nippon Kaiji Kyokai)
RINA (Registro Italiano Navale)
UL
(UL1604)
C
US
KEMA
Conformity Marking
1 TxD / 1 RxD, full/halfduplex
1200 ... 19200 baud
via differential signals
ca. 1000 m twisted pair
120 byte in / 16 byte out
65 mA
via system voltage DC /DC
500 V (System/Supply)
1 x 40 bits data
1 x 8 bits control/status
12 x 64* x 100
* from upper edge of 35 DIN rail
ca. 55 g
acc. to EN 50082-2 (96)
acc. to EN 50081-1 (93)
Cl. B
Cat. A, B, C, D
Env. 1, 2, 3, 4
Class I Div2 ABCD T4A
II 3 G EEx nA II T4
WAGO-I/O-SYSTEM 750