The Odu Power Feeder; Table 2-15: Odu Power Feeder Connectors; Table 2-16: Odu Power Feeder Leds - Nera WiLink-I Series System Manual

Modular base station
Table of Contents

Advertisement

2.3.2

The ODU Power Feeder

The ODU Power Feeder is used to provide power (-48 VDC) to AU-ODU-HP High
Power ODUs. It transfers transparently all signals between the AU-IDU and the
ODU, while injecting DC power received from an external source. Each ODU
Power Feeder unit can serve up to four High Power ODUs. Up to three ODU Power
Feeder units can be installed in a 1U high Power Feeder panel.
Name
IDU 1 - 4
ODU 1 - 4
-48V
(GND)
Name
PWR
ODU PWR 1 - 4
2.3.2.1
Preparing a Power Cable
A 2.5m DC power cable is supplied with each ODU Power Feeder module.
Additional DC cables can be ordered from the Supplier. If necessary, use the
following instruction to prepare a DC cable.
To prepare the power cable:
Use a cable capable of supporting a current of at least 10A. Use a cable with 2
1
x 10AWG (or thicker) wires for the power plus an additional 10AWG to 20AWG
ground wire.
WiLink-I Modular Base Station System Manual

Table 2-15: ODU Power Feeder Connectors

Connector
4 x TNC jacks
4 x TNC jacks
3-pin D-Type power jack
Grounding Screw

Table 2-16: ODU Power Feeder LEDs

Description
Input power indication
Output power indications
Installing the ODU Power Feeder
Functionality
Connection to ODU connectors of AU-IDUs/Micro Base
Station
Connections to IF connectors of AU-ODU-HP units
Connection to DC power source
Connection to ground (earth)
Functionality
¢
Off - ODU Power Feeder is not powered
¢
Green - ODU Power Feeder power is OK
¢
Off - AU-ODU-HP is not connected
¢
Red - Power output problem (short or overload)
¢
Green - AU-ODU-HP is connected and powered
51

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wilink-i 3000

Table of Contents