EC-fan High-voltage Tests

1.
Check Fuses. If fuses are okay, perform the following:
2. Check Fuses. If fuses are blown, perform the following:
NOTE: Power wires must be removed from the motor for resistance test.
Resistances should be similar for all 3 readings.
Resistance readings should be greater than 2 Ohm.
86
Check all connections.
Make sure connections are on the wire strand and not on the wire insulation.
Cycle Power. Disconnect mains voltage to power down the motor and then re-apply power.
Check mains voltage at each phase (phase to ground) at the KL1 connector. Confirm phase failure
not present.
Check that the voltage is within the acceptable voltage range at the KL1 connector. Confirm line
under-voltage is not present.
Check resistances across the phases at the KL1 connector and note them in the following table..
L1 -L2
L2 -L3
L1 -L3
Check all connections. Make sure connections are on the wire strand and not on the wire
insulation.
Replace Fuses.
Check mains voltage at each phase (phase to ground) at the KL1 connector. Confirms phase
failure not present.
Check that the voltage is within the acceptable voltage range at the KL1 connector. Confirms line
under-voltage is not present.
Ohm
Ohm
Ohm