9. Wrap lead wires once around new lamp's metal ends. This will support lamp and allow for thermal expansion.
Insert lead wires into junction block and torque screws to 30 in-lb.
10. Reassemble by reversing steps 1 through 9.
Figure 11.10 Infrared humidifier lamps
10.5 Condensate-drain and Condensate-pump System Maintenance
10.5.1 Condensate Drain
Check for and clear obstructions in tubing during routine maintenance.
10.5.2 Condensate Pump
WARNING! Risk of electric shock. Can cause injury or death. Open all local and remote electric
power-supply disconnect switches and verify that power is Off with a voltmeter before working
within the condensate pump electrical connection enclosure. The Liebert® iCOM™ does not
isolate power from the unit, even in the "Unit Off" mode. Some internal components require and
receive power even during the "Unit Off" mode of the Liebert® iCOM.
To maintain the condensate pump:
1.
Disconnect power to the unit using the disconnect switch.
2. Check for and clear obstructions in gravity lines leading to the condensate pump.
3. Remove the sump, clean with a stiff nylon brush and flush with water.
4. Inspect and clear clogs in the discharge check valve and float mechanism.
5. Reassemble and check for leaks.
100
Item
Description
1
Infraredbulbs
Vertiv | Liebert® CW™Installer/User Guide