Chilled Water Troubleshooting; Humidifier—Infrared Troubleshooting - Vertiv Liebert CW Series Installer And User Manual

Thermal management system
Table of Contents

Advertisement

Table 10.2  Chilled water troubleshooting
Possible
Symptom
Causes
No 24VAC
Actuator Motors
power to
motor
Motor
Chilledwater or hot
operatesbut
water/steam valve
valve won't
not opening
open
No 24VAC
power to
motor
ModulatingMotors
No signal
from control
Motor not
working
Table 10.3  Humidifier—infrared troubleshooting
Symptom
Possible Cause
Humidifier pannot filling
No
Control not callingfor
humidification
humidity
Humidity contact not
pullingin
Humidifier bulbburned
out
78
Check or Remedy
Check for 24VACbetweenP22-3 andP22-5 (open), or P22-1 andP22-5 (closed).
Check linkage for adjustment andbe sure that it istight onthe valve.
Check control fusesandpower at PCB andPCT.
Check DCvoltage onprintedcircuit boardinmotor. Terminal No. 1 isgroundedandNo. 3 ispositive. DCvoltage
shouldvary from 0.8to 2.0 VDCor above astemperature control isvariedbelowroom temperature oncooling
valve or above room temperature onheatingvalve.
Remove wiresonterminal No. 1 andNo. 3 from the motor (do not short). With24VACpower from TR to TR jumper
terminal 1 and2 onmotor to drive open. Remove jumper to drive closed, if motor failsto work, replace it.
Check or Remedy
Check water supply.
Check fill valve operation
Check drainstandpipe adjustment
Check for cloggedwaterline
Check float orientation(see )
Check monitor status
Check visually. If contact ismade, check line voltage after contactor andfusesor CBs.
Check for openhumidifier safety stat. Jumper betweenterminalsP35-6andP35-5. If contactor pullsin,
replace safety. Remove jumper.
Replace bulb. Loosenleadonoldbulb. Trim excessleadlengthonnewbulbto avoidshorts.
Vertiv | Liebert® CW™Installer/User Guide