2.6.1 Cooling, Dehumidification and Humidification
Return air to the unit must be no cooler than the ASHRAE recommendation of 68°F (20°C) DB and 40%RH or minimum WB
of 54°F (12.2°C) for proper unit operation. Operating below this can decrease equipment reliability.
2.6.2 Heating
The Liebert® CWis qualified for heating-only operation at temperatures not exceeding 80°F (27°C).
2.7 Shipping Dimensions and Unit Weights
Table 3.2 Shipping Dimensions
Model
038, 041
051, 060
076, 084
106, 114
146, 181
300, 400*
ModelsCW300 andCW400 shipintwo separate sections, eachisthe size shown.
Table 3.3 Shipping Weights
Model
038
041
051
060
076
084
106
114
146
181
300 *
400 *
*ModelsCW300 andCW400 shipintwo separate sections, eachweighinghalf of the amount shown.
2 Pre-installation Preparation and Guidelines
Domestic Packed, in. (mm)
55x40x76(1400x1020x1930)
77x40x76(1960x1020x1930)
102x40x76(2590x1020x1930)
125x40x80 (3180x1020x2030)
125x53x80 (3180x1350x2030)
125x53x80 (3180x1350x2030)
Domestic Packaging, lb. (kg)
840 (381)
890 (404)
1135 (515)
1200 (544)
1380 (625)
1480 (671)
1950 (885)
2090 (949)
2900 (1,314)
2900 (1,314)
5800 (2,628)
5800 (2,628)
Export Packed, in. (mm)
58x41x82 (1470x1040x2080)
80x41x82 (2030x1040x2080)
105x41x82 (2670x1040x2080)
128x41x82 (3250x1040x2080)
128x54x82 (3250x1370x2080)
128x54x82 (3250x1370x2080)
Export Packaging, lb. (kg)
1065 (483)
1115 (506)
1360 (617)
1425 (646)
1630 (739)
1730 (785)
2225 (1,009)
2365 (1,073)
3200 (1,450)
3200 (1,450)
6400 (2,900)
6400 (2,900)
21