Page 2
Technical Support Site If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. Visit https://www.VertivCo.com/en-us/support/ for additional assistance.
UPS system. Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. Turn the UPS off and unplug the Liebert MicroPOD before cleaning. Use only a soft cloth, never liquid or aerosol cleaners.
Page 5
WARNING! When the Liebert MicroPOD is in Utility position (maintenance bypass mode), the power to the connected load is not filtered or conditioned by the UPS. Vertiv | Liebert® MicroPOD ™ Installer/User Guide |...
Utility lamp indicates local power is available and the load may be transferred to bypass the UPS. UPS lamp indicates UPS power is available and the load may be transferred to the UPS to provide computer-grade power to the load. Vertiv | Liebert® MicroPOD ™ Installer/User Guide |...
The Liebert MicroPOD provides maintenance bypass capability as well as power output distribution. The Liebert MicroPOD can be used on UPSs in either rack mount or tower configuration. The Liebert MicroPOD provides an isolated path of power for your UPS system for preventive maintenance or service.
2. Inspect the Liebert MicroPOD for freight damage. Report any damage to the carrier and your local dealer or Liebert representative. 3. Verify that the Liebert MicroPOD input cord, UPS input cord and receptacle for the UPS have the same type of configuration.
(shipped with the Liebert MicroPOD). See Figure 2.5 on the facing page. 2. The rack mount brackets allow you to rack mount the Liebert MicroPOD in a 19" enclosure. 3. The Liebert MicroPOD can be mounted to face one of four directions depending on your application, utilizing the rack mount brackets provided.
Page 11
Figure 2.5 Liebert MicroPOD mounting bracket location CAUTION: Before installing, open all branch rated circuit breakers at the nearest disconnect, turn UPS off and disconnect all cords to and from the UPS. Vertiv | Liebert® MicroPOD ™ Installer/User Guide |...
The breaker is to be mounted within 6 feet (1.8m) of the Liebert MicroPOD and be readily accessible to the operator. Refer to on the facing page for breaker specifications.
CAUTION: To reduce the risk of fire, connect only to a circuit provided with properly rated maximum branch circuit overcurrent protection in accordance with the National Electric Code. For wiring information, refer to the following table. Vertiv | Liebert® MicroPOD ™ Installer/User Guide |...
Page 14
4. Inspect wiring to ensure it is not pinched. 5. Make connections to the terminal blocks as labeled. 6. Reattach the wiring access doors and reinstall the retaining screws. Figure 2.6 Removing plates to make hardwire connections Vertiv | Liebert® MicroPOD ™ Installer/User Guide |...
Page 15
9. Start the UPS according to its user manual. 10. Verify that the UPS lamp (green) on the Liebert MicroPOD is illuminated. If so, transfer the rotary switch from UTILITY to UPS. The load is now being supplied with conditioned power through the UPS.
This green lamp is illuminated when output power is available from the UPS (see Figure 2.7 below). It signals that it is safe to transfer connected loads from utility power back to UPS output power. Figure 2.7 Indicator lamps on Liebert MicroPOD Vertiv | Liebert® MicroPOD ™ Installer/User Guide |...
Reconnect the UPS to the Liebert MicroPOD. Start the UPS according to the instructions in the UPS user manual. 2. Verify that UPS lamp (green) on the Liebert MicroPOD is illuminated. If so, transfer the rotary bypass switch from UTILITY to UPS. If the lamp does not illuminate, refer to Troubleshooting page 21.
Page 19
Table 2.3 Specifications - Optional hardwire Liebert MicroPOD models MODEL # MP2-220N USED W/ LIEBERT GXT RATING, VA 3000 208V Dimensions, W x D x H, in (mm) Unit 15.51 x 5.2 x 5.2 (394 x 132 x 132) Shipping 19.29 x 8.66 x 10.63 (490 x 220 x 270)
Page 20
UL 1778, c-UL, ISTA Procedure 1A This Liebert MicroPOD is intended for use with a UPS meeting all the following requirements: • UPS input cord is compatible with the rating and type of receptacle on the Liebert MicroPOD labeled UPS. •...
PROBLEM CAUSE SOLUTION Call qualified service personnel to restore power to Utility not present. receptacle. Refer to Liebert MicroPOD installation instructions in this Utility lamp (amber) not illuminated. manual: Liebert MicroPOD input cord not connected to utility. • Installation on a Liebert GXT UPS on page 9 and •...