Watlow Integrated Controller User Manual Rev C EZ-ZONE PM User Manual page 13

Watlow ez-zone pm integrated controller user manual
Table of Contents

Advertisement

Slot A
Slot B
Output
Terminal Function
1
2
3
4
X1
X3
common (Any switched dc output can use this common.)
W1
W3
dc- (open collector)
Y1
Y3
dc+
W2
W4
dc-
Y2
Y4
dc+
F1
F3
voltage or current -
G1
G3
voltage +
H1
H3
current +
L1
L3
normally open
K1
K3
common
J1
J3
normally closed
L2
normally open
K2
common
L2
L4
normally open
K2
K4
common
L1
L2
L3
L4
normally open
K1
K2
K3
K4
common
Communications
CB
Modbus RTU EIA-485 T+/R+
CA
Modbus RTU EIA-485 T-/R-
CC
Modbus RTU EIA-485 common
CB
Modbus RTU EIA-485 T+/R+
CA
Modbus RTU EIA-485 T-/R-
C5
Modbus RTU EIA-232 common
C3
Modbus RTU EIA-232 to DB9 pin 2
C2
Modbus RTU EIA-232 to DB9 pin 3
V+
DeviceNet™ power
CH
Positive side of DeviceNet™ bus
SH
Shield interconnect
CL
Negative side of DeviceNet™ bus
V-
DeviceNet™ power return
E8
EtherNet/IP™ and Modbus TCP unused
E7
EtherNet/IP™ and Modbus TCP unused
E6
EtherNet/IP™ and Modbus TCP receive -
E5
EtherNet/IP™ and Modbus TCP unused
E4
EtherNet/IP™ and Modbus TCP unused
E3
EtherNet/IP™ and Modbus TCP receive +
E2
EtherNet/IP™ and Modbus TCP transmit -
E1
EtherNet/IP™ and Modbus TCP transmit +
Inputs
1
2
T1
T2
S2 (RTD) or current +, potentiometer wiper
S1
S2
S3 (RTD), thermocouple -, current - or volts -
R1
R2
S1 (RTD), thermocouple + or volts +
T2
mA ac
S2
mA ac
Terminal Definitions for Slots A and B.
Slot A
Slot B
Slot C
Slot B
or
®
Wat lo w EZ-ZO N E
P M I n te g r a t ed Co n t r o l l e r
Configuration
Switched dc/open collector
output 1: PM6 _ _ C _-_ _ _ _ A _ _
output 3: PM6 _ _ _ _-_ _ C _ A _ _
Switched dc
output 2: PM6 _ _ _ C-_ _ _ _ A _ _
output 4: PM6 _ _ _ _-_ _ _ C A _ _
Universal Process
output 1: PM6 _ _ F _-_ _ _ _ A _ _
output 3: PM6 _ _ _ _-_ _ F _ A _ _
Mechanical Relay 5 A, Form C
output 1: PM6 _ _ E _-_ _ _ _ A _ _
output 3: PM6 _ _ _ _-_ _ E _ A _ _
No-arc 15 A, Form A
output 2: PM6 _ _ _ H-_ _ _ _ A _ _
Mechanical Relay 5 A, Form A
output 2: PM6 _ _ _ J-_ _ _ _ A _ _
output 4: PM6 _ _ _ _-_ _ _ J A _ _
Solid-state Relay 0.5 A, Form A
output 1: PM6 _ _ K _-_ _ _ _ A _ _
output 2: PM6 _ _ _ K-_ _ _ _ A _ _
output 3: PM6 _ _ _ _-_ _ K _ A _ _
output 4: PM6 _ _ _ _-_ _ _ K A _ _
Modbus RTU 232/485 Communications
PM6 _ _ _ _-2 A A A A _ _
DeviceNet™ Communications
PM6 _ _ _ _-5 A A A A _ _
Ethernet 10/100 supporting EtherNet/IP™
and Modbus TCP
PM6 _ _ _ _-3 A A A A _ _
Universal Sensor
input 1: all configurations
input 2: PM6 _ _ _ _-_ (R or L) _ _ A _ _
Current Transformer
PM6 _ _ _ _-_ T _ _ A _ _
11