Kelvion KBloc Operating Instructions Manual page 40

Fully welded plate heat exchangers
Table of Contents

Advertisement

Setting up a horizontal-type K°Bloc delivered in horizontal position | standard K°Bloc
at the place of installation
Carry out the following steps:
1.
Remove the transport packaging, see section „5.3 Removing and
disposing of transport packaging" (page 30).
2.
Carefully lift the K°Bloc.
!
Make sure that you lift the K°Bloc only as high as necessary.
3.
Put down the K°Bloc carefully at its intended position.
4.
Anchor the K°Bloc to the foundation, using suitably dimensioned bolts
and nuts.
5.
Remove the two shackles and round slings from the lifting eyes above
the support angles.
The horizontal-type K°Bloc delivered in horizontal position | standard K°Bloc has
now been set up at the place of installation.
Done.
40
K°Bloc – Fully welded plate heat exchangers - English Version 2.2 - 01.2016