Parameter
Type of setting
number
d24
Heat/cool
changeover cooling
switch-point Heat/
cool changeover
cooling switch-
point Heat/cool
changeover cooling
switch-point
d25
Heat/cool
changeover heating
switch-point
d26
S1 - COM input
position
d27
S2 - COM input
position
d28
Service filter
d29
Protection heating
set point
d30
Protection cooling
set point
d31
Temperature display
resolution
d32
Cooling start delay
d33
Clock format
d34
ECO mode or
STANDBY mode.
When S2/COM
terminals are short –
thermostat will go to
ECO mode or
STANDBY mode.
d35
OFFSET of the second
sensor connected do
S2/COM (parameter
available only when
d03 = 2)
54
Fan Coil FC600 Instructions Manual
Description
The value of this parameter is used by the pipe
temperature sensor to switch to Heating mode. When
the temperature acquired by the sensor is above this
parameter's value, the thermostat will switch to heating
mode.
The value of this parameter is used by the pipe
temperature sensor to switch to Cooling mode. When
the temperature acquired by the sensor is below this
parameter's value, the thermostat will switch to cooling
mode.
0 = Normally open
1 = Normally close
0 = Normally open
1 = Normally close
The 'clean fan filter reminder' function counts the fan
operating hours. Is OFF or from 0.1 to 9.9 (9.9 means
9900hrs = 9.9*100)
OFF or from 5⁰C to 40⁰C (d29 value can not higher than
d30)
OFF or from 5⁰C to 40⁰C
This setting allows you change the temperature display
resolution.
0 = 0.1⁰C
1 = 0.5⁰C
From 0 to 15 minutes
0 = 12h
1 = 24h
0 = ECO mode
1 = STANDBY mode
For example when hotel card is in (occupancy sensor
indicates that person is in the room) – the thermostat
will go to ECO mode if you select "0", or go to STANDBY
model if you select "1"(for details, please see below)
From -3⁰C to +3⁰C
Default
Values
10⁰C
30⁰C
0
0
Off
8
Off
1
0
1
0
0⁰C