4.2 Modbus/TCP Mapping

The data map addresses of Advantech switches shown in the following table start
from Modbus address 30001 for function code 4.
In the given example, the address offset 0x1000 (hex) equals Modbus address
34097, while the address offset 0x1100 (hex) equals Modbus address 34353.
The information given by the Advantech is shown in hex mode.

4.2.1 Modbus/TCP Mapping Table

Catelog Name
System
Vendor ID
Info
= 0x'13FE
Unit ID =
0xFF
Product
Code
Vendor
Name =
"Advan-
tech"
Product
Name =
"EKI-xxxx"
Data Type
Interpr
etation
1 word 16 bits
HEX
1 word 16 bits
HEX
1 word 16 bits
HEX
16
32
ASCII
words
chars
16
32
ASCII
words
chars
44
Address
Address
Description
Offset
3X
(Hex)
0x0000
30001
Vendor ID = 0x13FE
0x0001
30002
Unit ID = 0xFF
0x0002
30003
Product Code
0x0010
30017
Vendor Name =
"Advantech"
Word 0 Hi byte = 'A'
Word 0 Lo byte = 'd'
Word 1 Hi byte = 'v'
Word 1 Lo byte = 'a'
Word 2 Hi byte = 'n'
Word 2 Lo byte = 't'
Word 3 Hi byte = 'e'
Word 3 Lo byte = 'c'
Word 4 Hi byte = 'h'
Word 4 Lo byte = '\0'
0x0020
30033
Product Name = "EKI-
xxxx"
Word 0 Hi byte = 'E'
Word 0 Lo byte = 'K'
Word 1 Hi byte = 'I'
Word 1 Lo byte = '-'
Word 2 Hi byte = 'x'
Word 2 Lo byte = 'x'
Word 3 Hi byte = 'x'
Word 3 Lo byte = 'x'
Word 4 Hi byte = '\0'
EKI-5729PI & EKI-5624PI User Manual