Chapter 7 Troubleshooting

7.2 Reset Request (Scan List Clear)

7
132
(1) The module is set in down mode after a reset request is issued.
START
Is down code other than F5H?
Yes
Replace the module. Read the down
information and send it together with
the module to TOSHIBA.
END
Figure 7-2 Reset Request Check Items
(2) The Module doesn't return to standby mode at the reset request of Scan List Clear.
When scan list clear is specified and when the scan list has not been set yet, it takes
about 9 seconds for the reset request to take effect. If it takes a longer time, switch
power back on.
If it takes 9 seconds or more for a reset request after switching power back on,
replace the module.
No
Stop input/output data read/write when
issuing a reset request.
model 2000 DeviceNet Module Manual (DN611/DN611A)