Toshiba 2000 V Series Manual page 59

Integrated controller module
Hide thumbs Also See for 2000 V Series:
Table of Contents

Advertisement

• Thin cable trunk line: 3 A maximum
Cable length
Maximum current
(A)
• Drop line: 0.75 to 3.0 A
I: Maximum current for drop line (A)
L: Drop line length (0 to 6 m)
6F8C0845
0m
10m
20m
3.00
3.00
3.00
Maximum current for thick
3.00
2.50
2.00
1.50
1.00
0.50
0.00
Figure 3-10 Trunk Line (Thin Cable) Current
Formula: I = 4.57/L (however, I<3 A)
30m
40m
50m
60m
2.06
1.57
1.26
1.06
細ケーブル最大電流
Cable lengthcable
ケーブル長
3.5 Network Power/Grounding
70m
80m
90m 100m
0.91
0.80
0.71
0.64
37
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Devicenet dn611Devicenet dn611a

Table of Contents