6.5 Setting up the power consumption control
EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1B – 2022.09
A Outdoor unit
B External backup heater kit
a1 Electrical cabinet: Normal kWh rate power supply
a2 Electrical cabinet: Preferential kWh rate power supply
b1 Power meter 1
b2 Power meter 2
c Overcurrent fuse
d Compressor module
e Hydro module
f Backup heater
S1S Preferential kWh rate power supply contact
You can use the following power consumption controls. For more information
about the corresponding settings, see
#
1
"6.5.1 Permanent power
▪
Allows you to limit the power consumption of the entire heat pump
system (sum of outdoor unit and backup heater (if applicable)) with one
permanent setting.
▪
Limitation of power in kW or current in A.
2
"6.5.2 Power limitation activated by digital
▪
Allows you to limit the power consumption of the entire heat pump
system (sum of outdoor unit and backup heater (if applicable)) via 4 digital
inputs.
▪
Limitation of power in kW or current in A.
3
"6.5.4 BBR16 power
▪
Restriction: Only available in Swedish language.
▪
Allows you to comply with BBR16 regulations (Swedish energy
regulations).
▪
Limitation of power in kW.
▪
Can be combined with the other kW power consumption controls. If you
do so, the unit uses the most restrictive control.
NOTICE
It is possible to install a field fuse with lower than recommended rating over the heat
pump. For this you must modify field setting [2‑0E] according to the maximum
allowed current over the heat pump.
Note that field setting [2‑0E] overrules all power consumption control settings.
Power limiting the heat pump will reduce performance.
NOTICE
Set a minimum power consumption of ±3.6 kW to guarantee:
▪
Defrost operation. Otherwise, if defrosting is interrupted several times, the heat
exchanger will freeze up.
▪
Space heating by allowing backup heater step 1.
"Power consumption
Power consumption control
4
limitation" [
44]
inputs" [
4
limitation" [
46]
6
Application guidelines
|
4
control" [
169].
4
44]
Installer reference guide