Setting Up The Power Consumption Control - Daikin EWYA004D2V3P Installer's Reference Manual

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWYA004D2V3P:
Table of Contents

Advertisement

6.5 Setting up the power consumption control

EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1B – 2022.09
A Outdoor unit
B External backup heater kit
a1 Electrical cabinet: Normal kWh rate power supply
a2 Electrical cabinet: Preferential kWh rate power supply
b1 Power meter 1
b2 Power meter 2
c Overcurrent fuse
d Compressor module
e Hydro module
f Backup heater
S1S Preferential kWh rate power supply contact
You can use the following power consumption controls. For more information
about the corresponding settings, see
#
1
"6.5.1 Permanent power
Allows you to limit the power consumption of the entire heat pump
system (sum of outdoor unit and backup heater (if applicable)) with one
permanent setting.
Limitation of power in kW or current in A.
2
"6.5.2 Power limitation activated by digital
Allows you to limit the power consumption of the entire heat pump
system (sum of outdoor unit and backup heater (if applicable)) via 4 digital
inputs.
Limitation of power in kW or current in A.
3
"6.5.4 BBR16 power
Restriction: Only available in Swedish language.
Allows you to comply with BBR16 regulations (Swedish energy
regulations).
Limitation of power in kW.
Can be combined with the other kW power consumption controls. If you
do so, the unit uses the most restrictive control.
NOTICE
It is possible to install a field fuse with lower than recommended rating over the heat
pump. For this you must modify field setting [2‑0E] according to the maximum
allowed current over the heat pump.
Note that field setting [2‑0E] overrules all power consumption control settings.
Power limiting the heat pump will reduce performance.
NOTICE
Set a minimum power consumption of ±3.6 kW to guarantee:
Defrost operation. Otherwise, if defrosting is interrupted several times, the heat
exchanger will freeze up.
Space heating by allowing backup heater step 1.
"Power consumption
Power consumption control
4
limitation" [
 44]
inputs" [
4
limitation" [
 46]
6
Application guidelines
|
4
control" [
 169].
4
 44]
Installer reference guide