Multiple Rooms - Two Lwt Zones - Daikin ETVH16UE6V7 Installer's Reference Manual

Table of Contents

Advertisement

6
|
Application guidelines
6.2.3 Multiple rooms – Two LWT zones
Installer reference guide
44
For more information about connecting the electrical wiring to the unit, see:
-
"9.2 Connections to the outdoor
-
"9.3 Connections to the indoor
For each room with heat  pump convectors: The heat  pump convectors are
directly connected to the indoor unit.
For each room with underfloor heating: Two shut-off valves (field supply) are
installed before the underfloor heating:
-
A shut-off valve to prevent hot water supply when the room has no heating
demand
-
A shut-off valve to prevent condensation on the floor during cooling operation
of the rooms with heat pump convectors.
For each room with heat pump convectors: The desired room temperature is set
via the controller of the heat pump convectors. There are different controllers
and setups possible for the heat pump convectors. For more information, see:
-
The installation manual of the heat pump convectors
-
The installation manual of the heat pump convector options
-
The addendum book for optional equipment
For each room with underfloor heating: The desired room temperature is set via
the external room thermostat (wired or wireless).
The user interface integrated in the indoor unit decides the space operation
mode. Mind that the operation mode on each external room thermostat and
controller of the heat pump convectors must be set to match the indoor unit.
INFORMATION
To increase comfort and performance, we recommend to install the valve kit option
EKVKHPC on each heat pump convector.
Configuration
Setting
Unit temperature control:
#: [2.9]
Code: [C-07]
Number of water temperature zones:
#: [4.4]
Code: [7-02]
If the heat emitters selected for each room are designed for different leaving water
temperatures, you can use different leaving water temperature zones (maximum
2).
In this document:
Main zone = Zone with the lowest design temperature in heating, and the highest
design temperature in cooling
Additional zone = Zone with the highest design temperature in heating, and the
lowest design temperature in cooling
4
unit" [
 109]
4
unit" [
 117]
0 (Leaving water): Unit operation is
decided based on the leaving water
temperature.
0 (Single zone): Main
Value
EPRA14~18D + ETVH16SU18+23E
Daikin Altherma 3 H HT F
4P644738-1D – 2023.10